PF3100 TROUBLESHOOTING – SOLUTIONS TO COMMON PROBLEMS
3.2

Swap a temperature or ignition module

If you need to change one or more temperature or ignition modules on an existing system you can perform the
following procedure.
1. Remove the old module.
2. Install the new module.
3. Update the system firmware to the desired version for all units. This is necessary for the replacement
module to talk to the rest of the system.
4. In the System Overview Settings screen open the Swap Wizard.
5. The swap wizard will list any hardware that is missing. Select the ignition or temperature module that you
would like to swap.
6. A dialog will appear that shows the existing configuration of the old module and a list of available
modules found to replace it.
7. Select a new module from the list.
8. If there is more than one module to swap you can select replacements for them now.
9. Press the right arrow when complete, a review page will show any issues. You will only be allowed to
apply the changes if there are no issues.
10. After applying the changes, the modules have successfully been swapped.
3.3

Swap a user interface

If you need to swap a user interface on an existing system perform the following procedure.
1. If the user interface is still accessible (not damaged) then backup the settings to a USB drive.
a.
In the System Overview Settings screen open the Backup Settings.
b. Save all system settings.
2. Remove the old user interface.
3. Install the new user interface.
4. Firmware update the system to the desired version.
5. If a backup of the settings had been previously made, you can now restore them.
a.
In the System Overview Settings screen open the Restore Settings.
b. Select the previously saved settings.
c.
Select all settings.
d. Review and load the new settings.
6. If a backup was not made the Appliance network map will now need to be updated.
a.
In the System Overview Settings screen open the Appliance Wizard.
b. Add a new appliance.
c.
Assign all the necessary controllers to it.
d. Review and apply the changes.
7. The user interface will now be successfully swapped.