Festo CPV E ASI-4E4A Series Brief Description page 17

Cpv valve terminal with as-interface

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 15
3
Installation instructions
3.1 Assigning the AS−Interface address
Please note
The AS−Interface address of the valve terminal type
CPV..−GE−ASI−4E4A−... is stored electronically (no bat
tery) after every modification and can be modified at
least 10 times. After that the valve terminal maintains
the last set AS−Interface address.
We recommend that you use the Festo addresser type ASI−
PRG−ADR with adapter cable type KASI−ADR.
Before connecting to the AS−Interface bus: assign an un
used address to each slave. Set the desired address with
the AS−Interface addresser. The permitted address range is
1 ... 31.
The factory setting of the terminal is address 0. It is not
necessary to parametrize the AS−Interface slaves.
Example of address assignment (Siemens S7)
AS−Interface adress #5, PLC byte #36
IO−Code 7
Input
PLC
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
...
...
36
...
...
...
Festo CPV..−GE−ASI−4E4A−... 0802d English
:
D3
D2
H
I/O
I/O
Output
res.
#1
res.
#2
#3
#4
#5
#6
#7
D1
D0
I/O
I/O
#1
#2
#3
#4
#5
#6
#7
= Assigned addresses
with IO code 7
H
17