4-6.1 Dslii Current Limiters; 4-6.2 Blown Limiter Indicator; 4-6.3 Fuse Truck - Eaton DSII Series Instructions For Installation, Operation And Maintenance

Low voltage power circuit breakers
Table of Contents

Advertisement

Effective July 2010
Table 4.1 Sensor and Limiter Ratings
Breaker
Sensor
Type
Rating
ø Recommended *Minimum
DSLII-308 800A
1600A
DSLII-308 600A
1200A
DSLII-308 Less than 1200A
600A
DSLII-516 1600A
3000A
DSLII-516 1200A
2500A
DSLII-516 Less than 2000A
1200A
DSLII-620 2000A
3000A
ø Minimizes nuisance blowing of limiters
* Use only when current limiting is required for downstream equip-
ment. If long delay pick-up is set above 100%, minimum limiter
ratings should not be used.
** Highest rating that will protect breaker.
trucks. They are used in series with DSII-632 and DSII-840
circuit breakers respectively. This separate mounting is made
necessary by the size of the fuses and their high tempera-
ture characteristics.

4-6.1 DSLII Current Limiters

Do not replace limiters with sizes other than permitted by
Table 4.1. DSLII current limiters have been tested and ap-
proved by Underwriters Laboratories, Inc. for use in DSLII
circuit breakers when applied according to Table 4.1. They
are not electrically or physically interchangeable with current
limiting fuses of any other design.
The current limiters are held in place in an extension
provided on the back of the circuit breaker (Figure 4-16).
This extension makes the DSLII circuit breaker eight inches
deeper than the corresponding DSII circuit breaker. The cur-
rent limiters can only be removed from the circuit breaker
and replaced when the circuit breaker is removed from its
associated compartment. For this reason there is no fixed
mounted version of the DSLII circuit breaker.

4-6.2 Blown Limiter Indicator

The blown limiter indicator provides a visual indication on the
front of the DSLII circuit breaker when a current limiter in
any phase has interrupted a short circuit. It also insures that
the circuit breaker will be tripped when any current limiter
has blown. This prevents single phase power from being ap-
plied to a three-phase load (Figure 4-17).
48
eaton corporation www.eaton.com
Limiter Ratings
**Maximum
1200A
2000A
800A
2000A
125% or more
2000A
of sensor rating
3000A
3000A
2000A
3000A
125% or more
3000A
of sensor rating
3000A
3000A
Instructional Book IB694C694-03
Figure 4-16 DSLII-516 Circuit Breaker (Side View)
The indicator device consists of three solenoids, each con-
nected in parallel with one of the limiters. When a limiter is
blown, the resulting voltage across the open limiter causes
the associated solenoid to operate. Operation of the sole-
noid trips the circuit breaker mechanically and extends an
indicator through the front cover of the circuit breaker (Fig-
ure 3-2). The indicator will remain extended and the breaker
will be held trip-free until the reset button is pushed. If the
device is reset and the breaker reclosed on an energized
circuit before the blown limiter is replaced, the breaker will
immediately be reopened and held trip-free. The solenoids
are isolated from the primary circuit voltage by three trans-
formers located above the limiters (Figures 3-2 and 4-16).

4-6.3 Fuse Truck

DSII-FT32 and DSII-FT40 fuse trucks provide drawout mount-
ing for current limiting fuses when installed in low voltage
switchgear. These drawout trucks physically fit in the same
compartment as the DSII-632 and DSII-840 circuit breakers
respectively. They are moved in and out of the compartment
using a similar levering mechanism as provided on DSII
circuit breakers (Figure 4-18 and 4-19).