OnOff Controller Installation (Continued)
6
OnOff Controller MCM-A200DN_IM_EN_03721A(1).indd 6
Different Levels of the OnOff Controller
Adjust the DIP switch in the OnOff controller PCB and set a level.
This will enable the user to control the indoor units
connected to the OnOff controller according to the set level.
SW22
Switch
No.
1
2
Among the various controllers, such as the OnOff
controller, wired/wireless controller and the indoor
LEVEL 0 OFF OFF
unit button, the air conditioner will only be able to
operate with the most recently used controller
The wired/wireless controller can only be used
LEVEL 1 ON OFF
when the OnOff controller is powered on.
The air conditioner can only be operated with
LEVEL 2 OFF ON
the OnOff controller.
RMC(1) address
DIP Switch
(SW01) = 0~F
SW22
SW21
Cooling
Heating
Cooling/Heating switch
Note
 The LEVEL of the OnOff controller is '0' when all the
switches are in the 'OFF' position.
 Changed LEVEL will be applied immediately when you
turn on or off the operation with an OnOff controller.
Level application and authorization for controlling from OnOff
controller can be restricted depending on the Level setting from
the upper controller with priority.
Ex) OnOff controller cannot control the indoor units if the control
level set from the DMS is higher than the level of
OnOff controller.
Meaning
SW22
SW21
OFF : Left
ON : Right