Dealing with malfunctions

In the event of malfunction or operating disturbances first check the points below:

Low room temperature during heating

Cause:
Compressor does not heat up.
Action:
Check and replace any blown circuit and main fu-
ses.
Cause:
The compressor does not start because of a too
low value set on the heating curve.
Action:
Check and possibly raise "Increase/reduce room
temperature" (knob on the front panel) or "Curve
slope".
Cause:
The compressor stands still due to the internal
overheating protection tripping.
Action:
Automatic resetting after cooling for a few hours.
Cause:
Possible earth circuit-breaker tripped.
Action:
Reset the earth circuit-breaker, if the earth circuit-
breaker trips repeatedly, call an electrician.

High room temperature during heating

Cause:
Incorrect setting of the "Curve slope" and/or
"Increase/reduce room temperature".
Action:
Adjust the setting.
NOTE
The product's serial number should always be stated
with all correspondence with NIBE.
_ _ _ _ _ _ _ _ _ _ _ _ _ _

Low hot water temperature or no hot water

Cause:
Large amounts of hot water were used.
Action:
Wait until the water heater reheats.
Cause:
Compressor and/or external additional heat does
not heat up.
Action:
Check and replace any blown circuit and main fu-
ses.
Cause:
Too low start temperature setting on the control
system (34).
Action:
Adjust the hot water setting "HW start", see
"Available information and on-display settings –
display 4".
Cause:
Possible earth circuit-breaker tripped.
Action:
Reset the earth circuit-breaker, if the earth circuit-
breaker trips repeatedly, call an electrician.
If the operating disturbance cannot be rectified by means of the above, an installation engineer should be called.

Low room temperature during cooling

Cause:
Compressor does not cool.
Action:
Check and replace any blown circuit and main fu-
ses.
Cause:
The compressor does not start because of a too
low value set on the cooling curve.
Action:
Check and possibly raise "Increase/reduce room
temperature" (knob on the front panel) or "Curve
slope".
Cause:
The compressor stands still due to the internal
overheating protection tripping.
Action:
Automatic resetting after cooling for a few hours.
Cause:
Possible earth circuit-breaker tripped.
Action:
Reset the earth circuit-breaker, if the earth circuit-
breaker trips repeatedly, call an electrician.
Low room temperature during cooling
Cause:
Incorrect setting of the "Curve slope" and/or
"Increase/reduce room temperature".
Action:
Adjust the setting.
NOTE
As FIGHTER 1127 can be connected to a large number
of external units, these should also be checked.

Helping the circulation pump to start

Shut off FIGHTER 1127 by setting the switch (8) to "0".
Open the service cover (Does not apply to the external
circulation pumps).
Loosen the venting screw with a screwdriver. Hold a cloth
around the screwdriver blade as a certain amount of
water may run out.
FIGHTER 1127
Miscellaneous
Dealing with malfunctions
Luftningsskruv
16
Venting screw