Page 1
(1550) 328-1550 kW ® Frontbild 27.08.2018 / O.Müller 4217901 Hoval products must be installed and commissioned Vertical gas condensing boilers UltraGas (1550) acc. ® by specialists only. These instructions are intended for to EN 15502-1/15502-2-1 are suitable and licensed for service engineers.
TABLE OF CONTENTS Important notices General safety instructions ..............................4 Explanation of the symbols ..............................4 1.2.1 Warnings ..................................4 1.2.2 Warning symbols................................4 1.2.3 Information ..................................5 On delivery ...................................5 Warranty ....................................5 Manuals ....................................5 Regulations, standards, ordinances to be complied with for proper use......................6 Installation Set-up ....................................7 Installation of the thermal insulation ..........................10...
Page 3
TABLE OF CONTENTS Maintenance Safety instructions ................................37 Deaeration ..................................37 Top up with water ................................37 Renewing fuse ...................................37 Information for fire inspector / chimney sweep regarding emission and manual operation settings ......38 Cleaning .....................................39 6.6.1 Cleaning the burner cylinder (inside and out) ........................39 6.6.2 Cleaning the combustion chamber and burner cylinder on the outside ................40 6.6.3...
IMpORTANT NOTICES Important notices Explanation of the symbols 1.2.1 Warnings General safety instructions The system may only be placed in operation if DANGER all the relevant standards and safety regulati- ... indicates a situation of immediate danger ons have been complied with. which will lead to serious or fatal injuries if not avoided.
Refers to standards and directives. Manuals All instructions relevant to your system can be found in the Hoval system manual - please keep all manuals! In exceptional cases, the instructions can be found with the components! Further sources of information: •...
IMpORTANT NOTICES Regulations, standards, ordinances to be Austria § • ÖNORM EN 12828 Heating systems in buildings - De- complied with for proper use sign of hot water heating systems The locally applicable heating system regulations must • ÖNORM EN 12831 Energy efficiency of buildings - be followed when planning, installing and operating the Method for calculation of the design heat load gas heat generator:...
INSTAllATION Installation Set-up WARNING The boiler must only be suspended using the four points marked as the crane suspension option in Fig. 02. The hooks on the back of the boiler must not be used to suspend it. Space requirement of UltraGas (1550) ®...
Page 8
INSTAllATION UltraGas (1550) with shortened boiler feet ® (All dimensions in mm) UltraGas ® Type (1550) 2457-2507 UltraGas (1550) with walled-in pedestal and adjustable feet ® UltraGas ® Type (1550) 2455-2505 1 Neutraliser / condensate box 2 Condensate pump 3 Walled base 4 Adjustable feet 30-80 mm UltraGas (1550) with walled-in pedestal without adjustable feet...
Page 9
INSTAllATION Procedure: 1. Remove front (5, Fig. 02) and rear (1) wooden crossbeam. 2. Using a winch (6), raise the front of the boiler. 3. Remove both side beams (2) to the front and side (see Fig. 02). 4. Push in front feet (3) and mount both front cover brackets (4). 5.
INSTAllATION Installation of the thermal insulation Place the insulation mat (1, Fig. 03) around the UltraGas (1550) boiler and attach with plastic straps (1a, Fig. 03) and ® strap fasteners (1b, Fig. 03). - Tension springs (1c, Fig. 03) are used for additional fixing - Do not overtighten the straps (reduced insulating value).
INSTAllATION Overview of casing sections The figure below shows the order in which the casing sections are mounted. Chapter “2.4 Fitting the casing” describes in detail the individual work steps of the mounting process for attaching the casings. Cable duct Side wall front with special screws Side wall back...
Fitting the casing 1. Hook the cable duct (1, Fig. 04) into the threaded pins on the left and right and attach with the second hexagon nuts and washers (1a) from the front already mounted on the boiler. If there is a side wall support (2, detail A), turn outwards to the side.
Page 13
Before hooking in the front cover (23), first take the steps listed in chapter “2.5 Fitting the pedestal ca- sing”. 14 a 13 a 13 a Detail C Exhaust gas sensor Mains cable Condensate box (if fitted) Water pressure sensor Pressure switch B17, B18 Flame monitoring (ionisation)
INSTAllATION Fitting the pedestal casing Attach the syphon (18, Fig. 07), which is sup- plied loose, including double nipple (18a). 11. Place the condensate box (option) under the boiler and establish the electrical connection. Make the condensate drain or connection line according to se- parate instructions.
(1550) is a low-pollution and ener- ® gy-saving gas condensing boiler with the Ultraclean bur- ner system, a gas-fired pre-mix burner with combustion air fan. The Hoval UltraGas (1550) has a vertically arran- ® ged combustion chamber of stainless steel as the primary...
TECHNICAl INFORMATION UltraGas (1550) technical data ® Type (1550) • Nominal heat output at 80/60°C, natural gas 298-1472 • Nominal heat output at 40/30°C, natural gas 328-1550 • Nominal heat output 80/60 °C, propane • Nominal heat output 40/30 °C, propane •...
TECHNICAl INFORMATION Dimensions / space required (All dimensions in mm) <( => 0:::: >- >- Notice For required space, see chapter 2.1. Fig. 11 10. Kondensatablauf mit Geruchsverschluss und Verschraubung für Kunststoffrohr 1. Vorlauf Heizung Heating flow Condensate drain with odour trap and screw connection for plastic pipe 11.
TECHNICAl INFORMATION 3.4.1 Overall unit dimensions Boiler without casing and insulation WARNING The boiler must only be suspended using the four points marked as the crane suspension option in Fig. 02. The hooks on the back of the boiler must not be used to suspend it. Fig.
® only works in conjunction with the TopTronic E/UG hea- ® Hoval UltraGas® (1550) ting controller. The automatic function device takes over the functions for correct operation of a modulating gas boiler. These are some properties that are integrated in the au- tomatic function device: •...
INSTAllATION Installation Requirements on the boiler room Safety instructions Regarding the building specifications for boi- § ler rooms, regulations specific to the state or country are to be observed. CAUTION Regarding the ventilation of boiler rooms, re- Cutting injuries as a result of sharp edges. gulations specific to the state or country are to Handle parts of the casing carefully and avo- be observed.
INSTAllATION Exhaust gas connection, exhaust gas • The cross sections and the maximum line lengths are calculated with reference to dia- Due to the low exhaust gas temperature, condensate grams or tables. The tables are available from forms in the exhaust gas line and wind protection equip- the exhaust gas line manufacturer.
INSTAllATION Condensate drain Option 3 + 4 (with outflow at a higher level) The boiler condensate drain must be made of • KB 24 Neutraliser box with pump corrosion-resistant including neutralisation material. The following materials are suitable • KB 22 Condensate box with pump for condensate discharge: •...
TECHNICAl INFORMATION Gas connection Hydraulic connection According to EN 12828:2003, the following safety-techni- cal equipment is integrated into the boiler: DANGER • Minimum pressure limiter DBmin Danger of explosion due to leaking gas con- • Safety maximum pressure limiter DBmax nection.
Actuator, mixer 2 • Install sacks to prevent single-pipe gravity circulation! NOTICE • An automatic air vent (AAV) must be ins- Please close unused connections tightly. talled before the shut-off valve. This is not supplied by Hoval. 4 217 901 / 02...
4.6.2.2 Cascades Procedure to remove the front casing 1. Remove front cover (1, image 18) after first releasing As a basic principle, the Hoval TopTronic E should per- ® the lateral locking bolt (1a) (turn approx. ¼ turn to the form cascade control.
TECHNICAl INFORMATION 4.8.1 Safety precaution for installation in line • Measures must be taken in the building and on electri- cal equipment to protect the units against overvoltage with EMC requirements caused by lightning strikes. • The mains connection for the heating system must be •...
Page 28
TECHNICAl INFORMATION In the case of star-shaped data bus networks, double To ensure correct electrical installation, unit connec- tion and equipotential bonding (energy supply com- earthing is not permitted. The earthing must be carried out on one side at the star point. pany and building installation), all applicable laws, regulations and standards must be complied with;...
TECHNICAl INFORMATION 4.8.2 Recommended cable cross-sections and maximum permitted cable lengths Line type Cross-section Length Electrical supply of min. 2.5 mm the heat generator unlimited m with 16 A fuse (230 V) Electrical supply of min. 2.5 mm the heat generator unlimited m with 16 A fuse (400 V)
• Risk of injury for non-expert personnel. • Initial start-up, maintenance and cleaning work are only allowed to be performed by trained specialist personnel or by Hoval customer service. NOTICE Damage to the system by filling unauthorised liquids.
In particular, attention must be paid to the following stipu- lations: Filling and replacement water • Hoval boilers and calorifi ers are designed for heating • For a plant using Hoval boilers untreated drinking water plants without signifi cant oxygen intake (plant type I ac- is generally best suited as heating medium, i.e.
INITIAl COMMISSIONING Venting the gas pipe Functional check of pressure monito- ring device Comply with the necessary regulations when § venting the gas pipe. WARNING Lack of combustion air and exhaust gas ac- cumulation can result in injury to persons. •...
6. Tighten upper screw on pressure switch B17. The settings must only be changed by a spe- 7. Correct pressure switch B17 or B18 settings if neces- cialist trained by Hoval or by Hoval customer sary (if the measured value differs more than 10% service.
1. Start the “Emission” menu on the control module. tion must only be made by a specialist trained - The control automatically switches to normal ope- by Hoval or by Hoval customer service. ration after expiration of the remaining runtime or after pressing the “Reset” button.
INITIAl COMMISSIONING Activation of screed function Description of function The control module of the TopTronic E contains a functional sequence used for drying out screed fl oors. To start the ® screed drying, it is necessary for the individual functions to be set accordingly. Flow temperature Heating-up phase Inertia phase...
Page 36
INITIAl COMMISSIONING Function display Icon Function Screed drying active Various settings can be made as well. Prioritisation of the screed func- tion means the settings are only ac- tive at the end of the function. Information remaining run time Request of the active function phase, the ACT temperature as well as the remaining run time.
Maintenance and cleaning work are only al- licensed electrician. lowed to be performed by trained specialist personnel or by Hoval customer service. 1. Set the blocking switch to “0” and disconnect the heat generator from the mains (main switch, fuse).
MAINTENANCE Information for fire inspector / chimney sweep regar- ding emission and manual operation settings This chapter is exclusively intended to describe the function of emissions and manual operation settings for the fi ring monitoring technician / chimney sweep. All operating elements are described in the operating instructions. CAUTION Danger of scalding with hot water, since the hot water temperature can exceed the target setpoint temperature.
The boiler is only allowed to be cleaned by a licensed specialist or Hoval customer service technician. The Hoval gas boiler must be cleaned and serviced at least once a year. NOTICE If the Hoval gas boiler was in operation during the building phase, it is essential to check the degree of contamination.
MAINTENANCE 11. Clean the premix burner inside and out with com- Preparation: pressed air or thoroughly flush with water. 12. Remove released dust and dirt particles with a vacu- WARNING um cleaner (4, Fig. 27). The heat generator must be de-energised for maintenance.
MAINTENANCE Fig. 30 Fig. 29 6.6.3 Cleaning/adjusting ignition and ionisation Cleaning: devices • Spray combustion chamber and aluFer pipes (3, Fig. ® The distance between the ionisation elec- 30). trode and the burner cylinder must be ap- - The best results are achieved with a spray gun and a prox.
MAINTENANCE Setting the gas quantity, measuring the CO ) and NOx/CO content in the exhaust gas (see chapter 5.8). Cleaning the syphon 21-UltraGas (850) Sifon • Release the syphon and remove it from the boiler. • Rinse the syphon. • Check syphon seal (1, Fig. 33) for damage and replace Fig.
Neutralisation granulate for refi lling the neutraliser box can be ordered from Hoval under the following item no.: Neutraliser box Type KB 23 • 1 pack (3 kg) neutralisation granules Part no.
WARNING Test port The settings must only be changed by a spe- cialist trained by Hoval or by Hoval customer service. 1. Check seat of the screw connections between pres- Sealing plug sure switch B18 and the burner cover:...
6.11 BIC 960 automatic function device´parameter list WARNING Changes to the BIC may only be made by authorised Hoval customer service technicians. The following table is intended solely to provide information for the Hoval customer service technician! 6.11.1 UltraGas (1550) automatic function device ®...
Page 46
MAINTENANCE Parameters Description Unit Level System setting values 45-UG (1550) 33 2FL 32801 Fan ramp-up during operation rpm/s 34 2FM 32802 Fan ramp-down during operation rpm/s 35 2FN 32803 Fan follow-on time after a lock-out 36 2FO 32804 Fan speed after shut-down 1600 in normal operation or when locked 37 2FR 32805 Fan follow-on time after operation...
Page 48
COPY FOR PLANT USER Confirmation The user (owner) of the system herewith confi rms that • he has received adequate instruction in the operating and maintenance of the installation, • received and taken note of the operating and maintenance instructions and, where applicable other documents con- cerning the heat generator and any further components.
Need help?
Do you have a question about the UltraGas 1550 and is the answer not in the manual?
Questions and answers