Outside units Information

Outside units Information
CAUTION
• Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each indoor unit capacity.
■ Combination Ration(50~200%)
Outside Number
Single outside units
Notes:
* We can guarantee the operation only within 130% Combination. If you want to connect more than
130% combination, please contact us and discuss the requirement like below.
1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all
the indoor units.
2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to
the Aheadquarter guidance.
3) Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
Power Supply: Outside Unit (3Ø, 460V, 60Hz)
■ Cooling Only
Unit
System Capacity (HP)
Combination Unit
Model
Independent Unit
Refrigerant Precharged Amount
Maximum Connectable Number of Indoor Units
Net Weight
Dimensions(WxHxD)
Liquid
Refrigerant
Connecting Pipes
Gas
Inlet
Water Connecting
Outlet
Pipes
Drain Outlet
Temp. range of
Cooling
Circulation water
8
Outside Unit
kg
kg
lbs
mm
inch
mm(inch)
mm(inch)
Connection Capacity
130%
1 Unit
10
ARWV100DAL4
ARWV100DAL4
2.0
16
127
279
755 × 997 × 500
29-23/32 x 39-1/4 x 19-11/16
9.52(3/8)
22.2(7/8)
PT25
PT25
PT20
10℃ ~ 45℃(50℉ ~ 113℉)