Dip switch setting
1. Set the dip switch and turn on the power of the outside unit to check whether the set value is correctly en-
tered in the 7 segment.
2. This function is shown for only 2 seconds after the power is connected.
n Checking according to dip switch setting
• You can check the setting values of the Master outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
• It checks whether the input is properly performed without the bad contact of the dip switch or not
n
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power.
This number represents the setting condition.
Master model capacity → Slave1 model capacity → Slave2 model capacity → Slave3 model capacity
→ Total capacity → System type → Power type → Product type
Example) 178 kW(62HP) 4Unit R410A combination (Cooling/heating switching type, 380V general type)
16 → 16 → 16 → 14 → 62 → 2 → 38 → 1
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
EX) Details of each symbol
Symbol
Number
8~20
10~20
10~20
10~20
8~80
1
2
3
38
46
22
1
2
3
Contents
Master model capacity
Slave 1 capacity
Slave 2 capacity
Slave 3 capacity
Total capacity
Cooling only
Cooling/Heating
switching type
Simultaneous
Cooling/Heating type
380 V
460 V
220 V
General type
Tropical type
Factory type
Model capacity
Capacity(kW) Capacity(HP)
23
8
29
10
35
12
41
14
46
16
52
18
57
20
Electrical Wiring
Remark
Refrigerant
Same
for master
R410A
/slave
Installation Manual 43