Outdoor Units Information - LG MULTI V III Solo ARUV100LM3 Installation Manual

Table of Contents

Advertisement

Outdoor units Information

Outdoor units Information
Power Supply: Outdoor Unit (3Ø, 380 - 415V, 50Hz / 3Ø, 380V, 60Hz)
Unit
System(HP)
Model
Product Charge
Max. Connectable No. of Indoor Units
Net Weight
Dimensions (WxHxD)
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
Unit
System(HP)
Model
Product Charge
Max. Connectable No. of Indoor Units
Net Weight
Dimensions (WxHxD)
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
n Combination ratio of indoor units : 50 ~ 130%
1. We can guarantee the operation only within 100% combination.
If you want to connect more than 100% combination, please contact us and discuss.
2. If the operation of indoor unit is more than 100%, the airflow is operated as low in the all indoor
units.
8
Solo
- Cooling only
10
ARUV100LM3
kg
5.0
16
kg
175 x 1
lbs
385 x 1
mm
(920×1,680×760) × 1
inch
(36-7/32 × 66-5/32 × 29-29/32) x 1
Ø 9.52(3/8)
Ø 22.2(7/8)
kg
kg
lbs
(1,240 x 1,680 x 760) x 1
mm
(48-13/16 × 66-5/32 × 29-29/32) x 1
inch
Outdoor Unit
1 Outdoor unit
ARUV120LM3
5.5
218 x 1
480 x 1
(920×1,680×760) × 1
(36-7/32 × 66-5/32 × 29-29/32) x 1
Ø 12.7(1/2)
Ø 28.58(1 1/8)
1 Outdoor unit
18
ARUV180LM3
6.5
29
325 x 1
717 x 1
Ø 15.88(5/8)
Ø 28.58(1-1/8)
12
ARUV140LM3
20
(920×1,680×760) × 1
(36-7/32 × 66-5/32 × 29-29/32) x 1
Ø 12.70(1/2)
Ø 28.58(1-1/8)
20
ARUV200LM3
6.5
32
325 x 1
717 x 1
(1,240 x 1,680 x 760) x 1
(48-13/16 × 66-5/32 × 29-29/32) x 1
Ø 15.88(5/8)
Ø 28.58(1-1/8)
14
5.5
23
218 x 1
480 x 1