Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions
Table 3 . Interrupting ratings
Trip-coil
Minimum-
Recloser
continuous
trip current
type
current (amps)
(amps)
5
10
10
20
15
30
E
25
50
35
70
50
100
70
140
100
200
50
100
70
140
100
200
4E
140
280
200
400
280
560
15
30
25
50
35
70
50
100
70
140
V4E
100
200
140
280
170
340
200
400
280
560
5
10
10
20
H
15
30
25
50
35
70
50
100
5
10
10
20
15
30
4H
25
50
35
70
50
100
70
140
100
200
5
10
10
20
15
30
25
50
35
70
V4H
50
100
70
140
100
200
140
280
200
400
Interrupting current
(rms symmetrical amps)
@24.9 kV
300
600
900
1500
2100
2500
2500
2500
3000
4000
4000
4000
4000
4000
900
1500
2100
3000
4200
6000
6000
6000
6000
6000
@2.4 through 14.4 kV
125
250
375
625
875
1250
@4.8
@8.32
@14.4
200
200
200
400
400
400
600
600
600
1000
1000
1000
1400
1400
1400
2000
2000
2000
2800
2500
2000
3000
2500
2000
200
200
200
400
400
400
600
600
600
1000
1000
1000
1400
1400
1400
2000
2000
2000
2800
2500
2000
3000
2500
2000
3000
2500
2000
3000
2500
2000
Trip-coil
Minimum-
Recloser
continuous
trip current
type
current (amps)
(amps)
25
50
35
70
50
100
L
70
140
100
200
140
280
200
400
280
560
15
30
25
50
35
70
50
100
V4L
70
140
100
200
140
280
170
340
200
400
280
560
OPERATION INSTRUCTIONS MN280051EN May 2017
Interrupting current
(rms symmetrical amps)
@4.8
@8.32
@14.4
1500
1500
1500
2100
2100
2100
3000
3000
3000
4200
4200
4000
6000
5000
4000
6000
5000
4000
6000
5000
4000
6000
5000
4000
@2.4 through 14.4 kV
900
1500
2100
3000
4200
6000
6000
6000
6000
6000