Ratings And Specifications - Eaton COOPER POWER E Installation And Operation Instructions Manual

Single-phase recloser
Table of Contents

Advertisement

Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions

Ratings and specifications

Table 1 . Ratings and specifications
Rated system
nominal
Recloser type
voltage (kV)
E
24.9
4E
24.9
V4E
24.9
H
14.4
4H
14.4
V4H
14.4
L
14.4
V4L
14.4
Table 2 . Rated interruptions
Recloser type
E
4E
V4E
H
4H
V4H
L
V4L
4
OPERATION INSTRUCTIONS MN280051EN May 2017
Rated system
max. voltage (kV)
27
27
27
15.0
15.5
15.5
15.5
15.5
% Interrupting rating
Maximum circuit X/R ratio
15-20
2
45-55
5
90-100
12
15-20
3
45-55
6
90-100
13
15-20
3
45-55
7
90-100
15
15-20
2
45-55
4
90-100
8
15-20
2
45-55
5
90-100
10
15-20
2
45-55
5
90-100
10
15-20
3
45-55
6
90-100
12
15-20
3
45-55
7
90-100
15
60 Hz Insulation level
Rated system
withstand rating
withstand voltage
(BIL) (kV)
Dry 1-Min. (kV)
150
60
150
60
150
60
95
35
110
50
110
50
110
50
110
50
Number unit operations
40
20
12
32
20
12
96
120
32
40
40
20
32
24
12
128
96
48
32
20
12
96
120
32
Continuous
Wet 10-Sec (kV)
current (amps)
50
100
50
280
50
280
30
50
45
100
45
200
45
280
45
280
Total unit operations
72
64
248
100
68
272
64
248

Advertisement

Table of Contents
loading