Troubleshooting
Abnormal condition
Indoor fan error
1. Error on outdoor temperature sensor (Short or Open)
2. Error on cond sensor
3. Error on discharge sensor
Other outdoor unit sensor error that is not on the above list
1. When there is no communication between the indoor∙outdoor units
for 2 minutes
2. Communication error received from the outdoor unit
3. 3 miniute tracking error on outdoor unit
4. Communication error after tracking due to unmatching number of
installed units
5. Error due to repeated communication address
6. Communication address not confirmed
Other outdoor unit communication error that is not on the above list
Self diagnosis error display
1. Error due to opened EEV (2nd detection)
2. Error due to closed EEV (2nd detection)
3. Eva in sensor is detached
4. Eva out sensor is detached
5. Thermal fuse error (Open)
1. COND mid sensor is detached
2. Refrigerant leakage (2nd detection)
3. Abnomally high temperature on Cond (2nd detection)
4. Low pressure s/w (2nd detection)
5. Abnomally high temperature on discharged air on outdoor unit (2nd
detection)
6. Indoor operation stop due to unconfirmed error on outdoor unit
7. Error due to reverse phase detection
8. Comp stop due to freeze detection (6th detection)
9. High pressure sensor is detached
10. Low pressure sensor is detached
11. Outdoor unit copression ration error
12. Outdoor sump down_1 prevetion control
13. Compressor down due to low pressure sensor prevention control_1
14. Simultaneous opening of cooling/heating MCU SOL valve (1st
detection)
15. Simultaneous opening of cooling/heating MCU SOL valve (2nd
detection)
Other outdoor unit self-diagnosis error that is not on the above list
Flowating s/w (2nd detection)
EEPROM error
EEPROM option error
Error due to incompatible indoor unit
● On
X Off
Flickering
If you turn off the air conditioner when the LED is flickering, the LED is also turned off.
If you re-operate the air conditioner, it operates normally at first, then detect an error again.
When E108 error occurs, change the address and reset the system.
Ex.) When address of the indoor unit #1 and #2 are set as 5, address of the indoor unit #1 will become 5 and indoor
unit #2 will display E108, A002.
46
Error code
Operation Defrost
E154
X
E221
E237
E251
E101
E102
E202
E201
X
E108
E109
E151
E152
X
E128
E129
E198
E241
E554
E450
E451
E416
E559
E425
E403
X
E301
E306
E428
E413
E410
E180
E181
E153
X
E162
E163
E164
LED Display
Timer
Filter
X
X
X
X
X
X