Select the power cable in accordance with relevant local and national regulations.
Wire size must comply with local and national code.
CAUTION
Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
You should connect the power cable into the power cable terminal and fasten it with a clamp.
The unbalanced power must be maintained within 10% of supply rating among whole indoor units.
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power
is exceeded over 10% of supply rating, the indoor unit is protected, stopped and the error mode
indicates.
To protect the product from water and possible shock, you should keep the power cable and the
connection cord of the indoor and outdoor units in the iron pipe.
Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be incorporated in the fixed wiring(≥3mm).
You must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and communication cable.
Maximum length of power cables are decided within 10% of power drop. If it exceeds, you must
consider another power supplying method.
The circuit breaker(MCCB, ELB) should be considered more capacity if many indoor units are connected
from one breaker.
Use round pressure terminal for connections to the power terminal block.
For wiring, use the designated power cable and connect it firmly, then secure to prevent outside
pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the terminal screws.
M3.5
0.8~1.2
M4
1.2~1.8
Tightening torque
N•m
kgf•cm
8.0~12.0
12.0~18.0
27