Advertisement

5. Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.
Indoor temperature of 30°C and humidity of 85% is the standard condition.
If installing in a high humidity condition, use one grade thicker insulator by referring to the table below.
If installing in an unfavorable conditions, use thicker one.
Insulator's heat-resistance temperature should be more than 120°C.
Pipe
Liquid pipe
Gas pipe
Ø28.58~Ø44.45
When installing insulation in places and conditions below, use the same insulation that is used for high humidity
conditions.
<Geological condition>
-
High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the building is
covered by earth and sand.)
<Operation purpose condition>
-
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
-
The ceiling frequently exposed to moisture and cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.
-
The place where the pipe is installed is highly humid due to the lack of ventilation system.
Insulation Type (Heating/Cooling)
Pipe size
[30°C, 85%]
Ø6.35 ~ Ø9.52
Ø12.7 ~ Ø50.80
Ø6.35
Ø9.52~Ø25.40
Ø50.80
Standard
High humidity
[30°C, over 85%]
EPDM, NBR
9t
13t
13t
19t
25t
Remarks
19t
Internal temperature is
higher than 120°C
25t
32t
38t
19