IBM 3745 Console Setup Manual page 141

Communication controller, nways multiprotocol controller
Table of Contents

Advertisement

Testing a Connection with the Local or Alternate Console
1. Turn on the operator console.
2. A CA INTERFACE DISPLAY screen similar to the following one should be
displayed (for the alternate console, wait 25 seconds):
-------------------------------- mm/dd/yy/ hh : mm
CA INTERFACE DISPLAY
INTERFACE
NUMBER
1A
2A
3A
4A
5A
5B
7A
SA
CHANGE
E/D
INTERFACE
HOST OR
CHANNEL
NSC
E/D REQ REQUEST STATUS SWITCH UNIT ADDRESS ADDRESS
==>
==>
==>
E
D
D
ENABLED
DISABLED
DISABLED
- TYPE E OR D TO CHANGE THE ENABLE/DISABLE REQUEST, THEN PRESS SEND
F4: MOSS FUNCTIONS
F5: UPDATE
3. If this screen displays, the console setup was successful.
40
41
42
4. If the screen is not displayed, check that the console cables are connected,
and that power is on, then try again to connect.
Other possible causes of a faulty console setup are as follows:
• The console is set to 1200 bps instead of 2400.
• The cable adapter
PIN
54F0490 is plugged wrongly. Check that the arrow
on the adapter pOints toward the console.
• The 3151 console is set up in both native and emulation modes.
If the problem continues, refer to the Problem Determination Guide, SA33-0096.
Note: You can also diagnose problems by using the console link test, as
described in the Problem Determination Guide.