F007
F008
F009
F010, F011
F012
F014
F016
F018
F019
F027
F028
F029
F030
TROUBLESHOOTING
SFC COMBI BOILERS SFC-99, SFC-125
No or insufficient flame current.
Incorrect fan speed
Internal fault in burner
controller.
Sensor fault S0.
Sensor fault S5.
Mounting fault sensor S0.
Mounting fault S3
Flue and/or air supply
duct is blocked.
Boiler Memory Module (BMM) fault.
Short circuit of outdoor
sensor S6.
Reset error.
Gas valve fault.
Sensor fault S3.
Check the ignitor.
Check the wiring of the ignitor for breakage/shutdown.
Replace the ignitor.
Check the fan cable.
Check and/or replace the fan.
Replace the burner controller.
Replace the burner controller.
Check the wiring of heat exchanger sensor S0 for
breakage/shutdown.
Check whether the heat exchanger sensor S0 is
connected correctly.
Check for the correct operation of heat exchanger
sensor S0.
Replace the heat exchanger sensor S0.
Check the wiring of flue gas sensor S5 for breakage/
shutdown.
Check whether the flue gas sensor S5 is connected
correctly.
Check for the correct operation of flue gas sensor S5.
Replace the flue gas sensor S5.
Heat exchanger sensor S0 is not mounted correctly.
Mount the sensor correctly.
Domestic hot water sensor S3 is not mounted
correctly. Mount the sensor correctly.
Check the flue and the air supply duct.
Clean the flue and/or the air supply duct.
Check BMM wiring for breakage/shutdown.
Replace the BMM.
Check the wiring of the outdoor sensor for breakage/
shutdown.
Replace the outdoor sensor.
BRINK WTW connection piece is connected. Burner
controller is unsuitable for this application. Replace the
burner controller with the correct version.
Check the reset button for unintentional operation (e.g.
cleaning of the control panel).
Replace the burner controller.
Check the gas valve for leakage.
Replace the burner controller.
Check the wiring of the domestic hot water sensor S3
for breakage/shutdown.
Check whether the domestic hot water sensor S3 is
connected correctly.
Check for the correct operation of domestic hot water
sensor S3.
Replace the domestic hot water sensor S3.
5-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sfc-125

Table of Contents