SFC 125 / SFB 125   -  Fuel Conversion to 
Propane - P-806
 
Note
If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P-
807) from your authorized IBC Distributor.
Use the Propane Gas conversion parts kit if the fuel source at the site uses Propane and the appliance has been 
set up   t o operate with Natural Gas. Check the rating plate on the boiler to see which fuel source the particular 
appliance has been set up with.
Using this conversion kit, a qualified technician will need to:
 1.  Perform a fuel conversion.
 2.  Perform a combustion test.
 3.  Fill in the information required on the fuel conversion labels, and affix them to the boiler after the 
conversion is completed.
Warning
This conversion kit shall be installed by a qualified service agency in accordance with the 
manufacturer's instructions and all applicable codes and requirements of the authority having 
jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or 
production of carbon monoxide may result causing property damage, personal injury or loss of life. 
The qualified service agency is responsible for the proper installation of this kit. The installation is not 
proper and complete until the operation of the converted appliance is checked as specified in the 
manufacturer's instructions supplied with the kit.
The boiler will automatically de-rate the maximum input at a rate of approximately 2% per 1,000' above 4,500'. 
The gas valve's zero-governor will ensure that the gas-air mixture is not affected at altitude.
Included with the Conversion Kit:
 
Part #
LP orifice # 370 
180-229
150-175 
Orifice   O -ring 19 x 2                          
080-305
Rating plate overlay 
080-107 
Gas valve conversion label 
080-244
Installer Identification label    
120-244E2
 
Description
 
Quantity
1
1
1
1
1
| 1

Advertisement

loading

Summary of Contents for IBC SFC 125

  • Page 1 SFC 125 / SFB 125   -  Fuel Conversion to  Propane - P-806   Note If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P- 807) from your authorized IBC Distributor. Use the Propane Gas conversion parts kit if the fuel source at the site uses Propane and the appliance has been  set up   t o operate with Natural Gas. Check the rating plate on the boiler to see which fuel source the particular  appliance has been set up with. Using this conversion kit, a qualified technician will need to:  1.  Perform a fuel conversion.  2.  Perform a combustion test.  3.  Fill in the information required on the fuel conversion labels, and affix them to the boiler after the  conversion is completed. Warning This conversion kit shall be installed by a qualified service agency in accordance with the  manufacturer’s instructions and all applicable codes and requirements of the authority having  jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or  production of carbon monoxide may result causing property damage, personal injury or loss of life.  The qualified service agency is responsible for the proper installation of this kit. The installation is not  proper and complete until the operation of the converted appliance is checked as specified in the  manufacturer’s instructions supplied with the kit. The boiler will automatically de-rate the maximum input at a rate of approximately 2% per 1,000’ above 4,500’.  The gas valve's zero-governor will ensure that the gas-air mixture is not affected at altitude. Included with the Conversion Kit:       Part # Description Quantity LP orifice # 370  180-229 150-175 ...
  • Page 2 Combustion Test Target Ranges Figure 1 Gas valve and fan The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in  the field unless indicated   i n these instructions.  After converting the appliance to propane, a combustion (CO ) reading must be taken by a qualified technician  using properly functioning and calibrated combustion analyzing equipment and the results compared to the values  in Table 1. Low Fire with front cover  Fuel High Fire with front cover open open 11.5% Actual Value at High Fire Minus  Max. CO  value - 0.3% 9.5% Min. CO  value 9.8% Table 1 - Combustion test target ranges - CO / Maximum CO...
  • Page 3: Fuel Conversion Instructions

    Model Number Orifice Size  /  SFC 16-125 SFB 16-125 Table 2 - Propane Orifice Chart To perform a fuel conversion:  1.  Turn off the gas supply at the manual gas valve.  2.  Disconnect the electrical power.  3.  Disconnect the nut at the gas valve outlet (top of the gas valve), and remove the O-ring and orifice.  4.  Insert the correct orifice into the O-ring, and re-install into the nut at the gas valve outlet (top of the gas  valve), and then tighten the nut.  5.  Restore the gas supply by opening the gas control valve.  6.  Test for leaks by using an approved leak detection solution on all joints.  7.  Power on the boiler / water heater appliance. Now, carefully follow the procedures on Combustion Testing and Adjustment. SFC 125 / SFB 125 - Fuel Conversion to Propane - P-806...
  • Page 4 Combustion testing and adjustment Danger A combustion test checks that the gas valve is operating properly in the field. To perform a combustion  test, you must be a qualified, trained and licensed gas fitter. Making adjustments to the gas valve without a properly calibrated gas combustion analyzer and by  people who are not trained and experienced in its use is forbidden. Failure to use an analyzer can  result in an immediate hazard. Model Number High Fire Input  /  125 MBH SFC 16-125 SFB 16-125 Table 3 Rated input of a converted boiler Normal ignition system sequence of operation: The boiler control, upon a call for heat or DHW, turns on the combustion fan for a 5-second pre-purge, then  energizes the spark electrode and gas valve for a 5-second trial for ignition. If the burner does not light, the process is repeated until the burner lights and flame is detected. After 4  unsuccessful trials for ignition, the appliance locks out and will need to be manually reset by pressing the Return  Arrow   button.  To perform a combustion test and adjustment:  1.  Turn off the appliance’s manual gas valve.   2.  With a Torx 15 screwdriver, open the inlet gas supply pressure test port by  turning its screw 1 full turn counterclockwise.  3.  Attach a manometer to the inlet pressure test port and turn on gas to  appliance. Static manometer reading should be ideally   1 1" w.c. for Propane. Minimum and maximum static pressure must be between 5" and 14" ...
  • Page 5  and counter-clockwise to reduce CO . If the target cannot be met, even after a half  turn, contact the factory.   c.  When finished, replace the Low Fire cap, and leave the manual mode by pressing + AND -  simultaneously.  7.  Switch off the appliance by pressing the space above the dot.   8.  Turn off the gas at the appliance's manual gas valve.  9.  Remove the flue gas analyzer from the test port, and reinstall the test port cap.   10.  Remove the gas pressure manometer from the gas valve, and fully close the test port.  11.  Turn on the gas at the appliance’s manual gas valve.  12.  Ensure there are no gas leaks before reinstalling the front cover.   13.  Turn on the appliance by pressing the space above the dot. Next you must fill in the information and affix the included fuel conversion labels to the boiler as indicated after  the conversion is completed. Completing and Affixing the Conversion Labels  1.  Fill in the conversion labels (included in the kit) associated with the new fuel type.  2.  Place the conversion labels onto the boiler as indicated below. SFC 125 / SFB 125 - Fuel Conversion to Propane - P-806...