6 MAINTENANCE

6.6.3 CPU indicators display messages

With the S10mini, one of the messages listed below is displayed in the CPU module indicator
when a certain event or error occurs in the SD.LINK module.
The S10V collects error information, but does not display errors on the LPU module. Error
information collected can be referenced from Error Log on S10V Basic System. For more
information, refer to "S10V USER'S MANUAL BASIC MODULES (manual number SVE-
1-100)."
Error code
Message
(S10V)
(S10mini)
SD□ x.x
0x0010
SD□ BUS
0x0011
SD□ ADDR
0x0012
SD□ ILLG
0x0013
SD□ ZERO
0x0014
SD□ PRIV
0x0015
SD□ WDT
0x0016
SD□ FMAT
0x0017
SD□ SINT
0x0018
SD□ EXCP
0x0019
SD□ PTY
0x001A
SD□ GR
0x0100
SD□ MDSW
0x0101
SD□ CPSW
0x0102
SD□ ROM1
0x0103
SD□ RAM1
0x0105
SD□ RAM2
0x010B
SD□ ROM3
0x010C
SD□ ROME
0x010D
SD□ ROMW
0x010E
SD□ ROME
0x010F
SD□ ROMW
0x0110
0x0111
SD□ DPCP
0x0112
SD□ PRME
□=M: Main module
□=S: Submodule

Table 6-3 CPU Indicator Display Messages

Explanation
Normal operation
Bus error
Address error
Illegal instruction
Division by 0
Privilege violation
WDT error
Format error
Spurious interrupt
Unused exception
Parity error
GR announcement
Module number setting switch
error
CPL number setting switch error Set the CPL number switch to a valid value. (See
ROM1 checksum error
RAM1 compare error
ROM2 compare error
ROM3 checksum error
ROM3 erase error (program)
ROM3 write error (program)
ROM3 erase error (parameter)
ROM3 write error (parameter)
ROM rewrite count over
Duplicate CPL number
Parameter error
This is not an error. (x.x denotes version and
revision numbers.)
Reset the module. If the same error message
recurs, the SD.LINK module may have failed.
Replace the module.
Set the module number switch to a valid value.
(See "2 NAMES AND FUNCTIONS OF EACH
PART.")
"2 NAMES AND FUNCTIONS OF EACH
PART." and "4.2 Setting Switch.")
Reset the module. If the same error message
recurs, the SD.LINK module may have failed.
Replace the module.
Reset the module and set parameters. If the same
error message recurs, the SD.LINK module may
have failed. Replace the module.
Replace the module.
Set a unique CPL number. (See "2 NAMES
AND FUNCTIONS OF EACH PART." and "4.2
Setting Switch.")
Set the parameters again. (See "4.6
Commands.") To find out more , see the next
page.