(chapter 2, page 2-2)
Up to two units of the SD.LINK (LQE030/530) module and the OD.RING
(LQE010/015/510/515) module can be intermixed. Set the module number
setting switch on either module to main and that on the other to sub.
If the module number setting switch is set to 'E' or 'F' and then the power to
the SD.LINK module is cycled or it is reset, its error LED will glow but this is
not a sign of fault.
(chapter 3, page 3-2)
S10mini Series
Mount the option module in option slots that is located to the immediate right of
the CPU module. Be sure that no I/O module is mounted between this option
module and CPU module. Also, ensure that there is no unoccupied slot
between option modules.
This module (LQE530) can be mounted together with the LQE030 SD.LINK
module, which is specially designed for use with the S10mini.
S10V Series
There are no specific rules about the mounting position or unoccupied slots.
The LQE030 SD.LINK module cannot be used as it is specially designed for
use with the S10mini.
NOTICE
NOTICE
S-8