SUN2000-(100KTL, 110KTL, 125KTL) Series
User Manual
No.
Cable
AC output
power cable
(single-core)
● The value of S
is valid only if the conductors of the PE cable and AC power cable use the
p
same material. If the materials are different, ensure that the conductor of the PE cable with a
proper cross-sectional area produces a conductance equivalent to that of the cable specified in
the table.
● The specifications of the PE cable are subject to this table or calculated according to IEC
60364-5-54.
● The cable diameter must comply with local cable standards.
● The factors that affect cable selection include the rated current, cable type, routing mode,
ambient temperature, and maximum expected line loss.

5.3 Connecting the PE Cable

Context
● Proper grounding is helpful for resisting the impact of surge voltage and
● It is recommended that the PE cable of the solar inverter be connected to a
Procedure
Step 1 Connect the PE cable to the PE point.
Issue 07 (2020-09-15)
Category
You are advised to use a
single-core outdoor cable
and M12 OT/DT
terminals.
NO TICE
improving the electromagnetic interference (EMI) performance. Before
connecting the AC power cable, DC power cables, and communications cable,
connect the PE cable to the PE point.
nearby ground point. Connect the PE points of all solar inverters in the same
array to ensure equipotential connections to PE cables.
Copyright © Huawei Technologies Co., Ltd.
Conductor
Outer
Cross-Sectional
Diameter
Area Range
● Copper cable:
14–32 mm
– S: 70–240
2
mm
● Aluminum
alloy cable or
copper-clad
aluminum
cable:
– S: 95–240
2
mm