For 1P2W1M wiring, connect a voltage measurement channel between the phase line and the zero
line; connect a current measurement channel in series with the phase line or the zero line (note the
direction) or clamped on the phase line or the zero line with a current sensor.
3P4W3M
For 3P4W3M wiring, 3 voltage measurement channels are respectively connected between each
phase line and the zero line; 3 current measurement channels are respectively connected in series
with each phase line or clamped on each phase line with a current sensor.
For systems without zero lines, connect 3 voltage measurement channels between the 3 phase lines
and the common ground line. For a 3P5W system, you can use a wiring group of 3P4W3M to
measure the phase and zero line. You can select one channel and configure it as 1P2W1M to
24
Figure 8.
1P2W1M Wiring
Figure 9.
3P4W3M Wiring