Commissioning
1. Open the valve fully by turning the white
protection cap about one turn.
2. Set the volume flow of the surface heating
circuit with the help of the regulating insert
(see section 3.4.1 on page 26).
Control the flow temperature via
the heat generator control.
3. Start with a flow temperature between
20°C and 25°C for at least 3 days.
4. Then heat at the maximum design flow
temperature for at least 4 days.
7.4 Installation of the thermostat
with remote control
1. After having completed all building work,
remove the protection cover of the "Unibox
E BV vario".
2. Remove the protection cap.
3. Screw the control piston (see Illust. 8 on
page 30 (1)) onto the valve. Direct the
capillary downwards.
The capillary must not be kinked.
1
Illust. 8: Installation of the thermostat with
remote control
(1)
Control piston
(2)
Thermostat with remote control
30
4. Fit the cover to the "Unibox E BV vario".
7.5 Installation of the room
thermostat with actuator
1. After having completed all building work,
remove the protection cover of the "Unibox
E BV vario".
2. Remove the protection cap.
3. Screw the extension (see Illust. 9 on page
30 (3)) onto the valve.
4. Screw the actuator (see Illust. 9 on page
30 (1)) onto the valve. Feed the cable
through the hole in the wall box unit (see
section 6.1 on page 27).
2
Illust. 9: Installation of the room thermostat
(1)
Actuator
(2)
Room thermostat
Unibox E BV vario
The cover is not included in the
extent of supply and has to be
ordered separately (see section 4
on page 26).
For further information please refer
to the operating instructions sup-
plied with the actuator.
1
with actuator
102272580-V01.04.2020