Download Print this page

Siemens Desigo DXR1.E02PLZ-112 Manual page 6

Compact actuating room automation station, bacnet/ip, ac 24 v (actuating dxr)

Advertisement

Technical data
Power data
Power supply
Operating voltage (SELV/PELV)
Frequency
Power consumption
Transformer requirements and recommended voltages
Type
Functional data
Functional data
Nominal torque
Nominal rotary angle
Maximum rotary angle
Runtime for 90° rotary angle
Shaft size
Minimum shaft length
Pressure sensor
Pressure sensor
Measurement range
Sample rate
Overload range
Measuring range accuracy
Zero point accuracy
Resolution
Connections
Interfaces
Ethernet
USB (2.0)
Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Design type
6
Siemens
Smart Infrastructure
AC 24 V +/-20%
50 or 60 Hz
6.5 VA max.
Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV
10 Nm
90°
95° ± 2°
150 s
8...16 mm, round
8...10 mm, round (with centering insert)
6...12.8 mm square
20 mm
0...500 Pa
≤ 500 ms
0...100 kPa
3%
0.2 Pa
12 Bit
Plugs: dual RJ45, 10M/100M fast Ethernet
Interface type: IEEE 802.3 compliance
Cable type: 100M STP CAT 5
Type Micro B
Type 1
2
III
Device suited for use with equipment of safety
A6V11393935_en--_c