Download Print this page

Siemens Desigo DXR1.E02PLZ-112 Manual page 4

Compact actuating room automation station, bacnet/ip, ac 24 v (actuating dxr)

Advertisement

Notes
Security
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Use only properly trained technicians for mounting, commissioning and servicing.
Engineering
Identification
Each device has a unique serial number to ensure efficient commissioning. It is provided on
the adhesive barcode reader. The serial number can be read directly into the engineering
tool using a barcode reader.
Wiring
Wiring must be sufficiently insulated to the available rated voltage. Sizing and fusing of the
wiring depends on the connected load.
Mounting
The automation station is mounted directly on a damper shaft.
See the mounting instructions (document ID: A6V11393918) for detailed information.
Differential pressure sensor
Avoid bends and pressure when attaching the tube.
Connect the "+" connection on the side with the higher pressure and the "-" connection
on the side with the lower pressure.
Connection tubes (interior diameter) of 4 mm.
Accessory kit DXA.T50 for connection tubes (interior diameter) of 6.5 mm.
4
Siemens
Smart Infrastructure
CAUTION
A6V11393935_en--_c
2020-09-01

Advertisement

loading

This manual is also suitable for:

S55499-d460