AD-1252 Thermal Dispersion Probe Airflow Measuring
System
Installation Instructions
Applications
The AD-1252 Thermal Dispersion Probe Airflow
Measuring System is an air-measurement device that
uses thermal dispersion technology to measure the
airflow velocity and temperature in duct and plenum
applications. Insertion probes are typically installed in
retrofit applications but may also be specified on new
construction projects.
The product may be used in rectangular, oval, or round
applications when installed in accordance with this
installation manual. Use behind a rain hood, in front of
an outside air damper, return air duct, downstream of a
fan discharge, or in the exhaust duct.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Refer to the
AD-1252 Thermal Dispersion Probe Airflow Measuring System
Installation Instructions
4 4 - 1 1 2 2 - 2 ,
QuickLIT website
for the most up-to-date version of this document.
Installation
IMPORTANT: Do not connect CAT5e cable to a
router between the DMPR-RA002 Electronic
Controller and thermal dispersion probes. Failure to
connect the cables directly from the DMPR-RA002
Electronic Controller to the thermal dispersion
probes may cause equipment damage.
IMPORTANT: In addition to these instructions, the
installation contractor shall comply with all local and
International codes and standards to ensure proper
and safe installation.
The thermal dispersion probes and electronic controller
ship in separate containers. Remove the thermal
dispersion probes and the electronic controller from the
shipping containers and inspect the devices for
damage before installation.
Installing the Thermal Dispersion Probes
The sensor density is based on extensive lab testing to
optimize the accuracy of the electronic controller.
When installing the thermal dispersion probes, use the
Square Duct Mounting, Round Duct Mounting, and
Oval Duct Mounting sections to determine the proper
spacing between each probe within the opening.
Contact your local Johnson Controls® representative if
you have questions regarding a particular application.
WARNING: Risk of Electric Shock.
Disconnect the power supply before making
!
electrical connections. Contact with
components carrying hazardous voltage can
cause electric shock and may result in severe
personal injury or death.
AVERTISSEMENT : Risque de décharge
électrique.
Débrancher l'alimentation avant de réaliser
tout branchement électrique. Tout contact
avec des composants conducteurs de
tensions dangereuses risque d'entraîner une
décharge électrique et de provoquer des
blessures graves, voire mortelles.
1
Re v .
G
Part No. 44-1122-2, Rev. G
Issued June 2016

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls AD-1252

  • Page 1 Règlement sur le matériel avec des composants conducteurs de brouilleur du Canada. tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 2 Damage to the product resulting from not following the instructions or using unauthorized parts may be excluded from the manufacturer’s warranty coverage. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 3 The minimum diameter size is 12 x 12 inches for rectangular duct applications. Sizes less than 12 x 12 in. (304 x 304 mm) use the same number of probes and sensors as the 12 x 12 in. (304 x 304 mm) size. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 4 The minimum diameter size is 12 inches for round duct applications. Round duct applications smaller than 12 inches (304 mm) use the same number of probes and sensors as the 12 inches (304 mm) size. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 5 Oval Duct Mounting Figure 5: Oval Duct Mounting - Sensor Density Details Table 3: Number of Probes/Sensors per Probe for Oval Duct Applications Duct Duct Width, in. Height, in. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 6: Location Considerations

    H + W Example: 35 in. length x 20 in. width rectangular duct D = 2 x (35 x 20) / (35 +20) D = 1, 400 / 55 D = 25.46 AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 7 3 in. (76 mm) holes until the probe mounting stud extends through the 2 in. (50 mm) holes in the opposite side of the duct. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 8 Note: Box provided may appear different than the example above. Figure 11: Probe with Internal Mounting Bracket Figure 9: Probe with Standard Insertion Mounting Hardware (Hoods Shown on Top for Illustrative Purposes)   AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 9: Cable Specifications

    Table 5: Pin Numbers and Corresponding Wire Colors for Simple Pairing Pin Number Wire Color White and Green Green White and Orange Orange White and Blue Blue White and Brown Brown AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 10: Finishing The Installation

    22 AWG. Larger gauge wire may be required for long runs. All wiring must 5. After configuring the electronic controller, replace comply with applicable codes. the cover. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 11: Setup And Adjustments

    ESC button to exit. If you are using firmware version 8.4 or higher, you return to the factory default or previous setting. If you are using a firmware version prior to 8.4, the values change to zero. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 12 This option submenu turns the LCD screen on the Figure 17: Error Indication Submenu electronic controller ON or OFF. See Figure 16. ERROR INDICATION ENTER ERROR INDICATION ENTER TEST SIGNAL :OFF DOWN ERROR INDICATION ENTER TEST SIGNAL AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 13 If the test signal at the controller is not correct, contact the factory for additional calibration DOWN procedure instructions. 10mA TEST SIGNAL UNITS ENTER HOLD ESC TO EXIT DOWN 20mA TEST SIGNAL UNITS ENTER HOLD ESC TO EXIT AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 14 VELOCITY UNIT VELOCITY UNIT :M/S :L/S DOWN ENTER ENTER VELOCITY UNIT VELOCITY UNIT :FPM :CFM DOWN ENTER ENTER DOWN AREA VALUE :1.00 sq.M. ENTER DOWN AREA VALUE :1.00 sq.ft. GAIN ENTER GAIN AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 15 Do not select extremes that are outside expected normal operating conditions. For example, if winter design conditions are approximately 65% and summer design conditions are 95%, those two points would be calibration points. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 16 (A - B) Gain A = Value calculated in Step 7. B = Value calculated in Step 4. C = Value calculated in Step 6. D = Value calculated in Step 3. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 17 Submenu with Velocity Unit: FPM Selected SCALE VELOCITY mA OUTPUT SIGNAL ENTER 20mA VALUE 20mA VALUE :40 FPM :4000 FPM DOWN ENTER 4mA VALUE 4mA VALUE :40 FPM :4000 FPM DOWN ENTER RESET SETTINGS AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 18: Troubleshooting

    See Figure 12. If the right (amber) LED does not blink, reset the electronic controller by cycling the power switch OFF and then ON. See Figure 12. AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 19 9 through 12 Right Input 13 through 16 Use Table 7 to troubleshoot problems with the AD-1252 System. Table 7: AD-1252 System Troubleshooting (Part 1 of 3) Problem Possible Cause Corrective Action The LCD screen displays the units The transmitter is in calibration mode.
  • Page 20 Table 7: AD-1252 System Troubleshooting (Part 2 of 3) Problem Possible Cause Corrective Action The LCD screen does not display The ZERO CUTOFF value is set 1. Record all settings for gain, square below certain values. incorrectly. feet, offset, 20 mA and 4 mA values.
  • Page 21 Table 7: AD-1252 System Troubleshooting (Part 3 of 3) Problem Possible Cause Corrective Action The LCD screen indicates a large Multiple probes are trying to Cycle power to the control transmitter. negative FPM and then cycles to a communicate with the electronic Check the flashing lights.
  • Page 22: Repair Information

    10-foot shielded CAT5 cable DMPR-RA022 20-foot shielded CAT5 cable DMPR-RA023 30-foot shielded CAT5 cable DMPR-RA024 40-foot shielded CAT5 cable DMPR-RA025 50-foot shielded CAT5 cable DMPR-RA026 15-foot shielded CAT5 cable DMPR-RA027 25-foot shielded CAT5 cable AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 23: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.