Room Pressure Monitor
Installation Instructions
LB-FMS1655M-S01
LB-FMS1655M-T01
Application
These installation instructions guide the installer through the installation of the FMS-1655M Room Pressure Monitor.
Please read these instructions thoroughly before beginning installation.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
NOTICE
Risk of Property Damage.
Ensure that the power source conforms to the requirements of the equipment. Failure to use a correct power source may result in
permanent damage to the equipment.
NOTICE
Risque de dégâts matériels.
S'assurer que la source d'alimentation électrique est conforme aux spécifications de l'équipement. L'utilisation d'une source
d'alimentation électrique inappropriée risque d'endommager irrémédiablement l'équipement.
IMPORTANT:
The FMS-1655M Room Pressure Monitor must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause
serious damange and void the warranty.
Use of the software that is in (or constitutes) this product or access to the cloud or hosted services applicable to this product, if any,
is subject to applicable terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to
such terms. If you do not agree to be bound by such terms, you may return the unused product to your place of purchase.
1
LIT-12013119
January 2019

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls FMS-1655M

  • Page 1 électrique inappropriée risque d’endommager irrémédiablement l’équipement. IMPORTANT: The FMS-1655M Room Pressure Monitor must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause serious damange and void the warranty. Use of the software that is in (or constitutes) this product or access to the cloud or hosted services applicable to this product, if any, is subject to applicable terms set forth at www.johnsoncontrols.com/techterms.
  • Page 2 FMS-1655M FMS-1655M Room Pressure Monitor settings This form should be completed during the initial configuration for each room pressure monitor. Be sure to configure the unit for either Positive, Negative, or both using the Isolation Mode Configuration setup procedure. Room Name / Number...
  • Page 3: Table Of Contents

    FMS-1655M Table of contents General ......................................4 Specifications ..................................4 Part Number Guide ................................5 Overview ....................................8 Mounting/Wiring ..................................9 Installation ....................................9 Remote sensor mounting procedure ............................9 Display mounting procedure (surface mount) ........................10 Flush thin mount mounting procedure ..........................11 Installation detail view ................................
  • Page 4: General

    Stainless Steel Cover Plate for Remote Sensor ………………………….……………………………………..……… 2.7”W x 4.5”H x 0.2”D Surface Mount FMS-1655M Monitor with Power Supply ………………..……………………………….……...…..…… approx. wt. 3.7 lb. Flush Thin Mount FMS-1655M Monitor with Power Supply ………………..…………………………………..……… approx. wt. 5.4 lb. FMS-1655M Monitor Mounting Options ………………………………..……………………………………………...……… Surface, Flush Flow Tube Cover Plate Mounting …………………………..………………………………………………...………….…...
  • Page 5: Part Number Guide

    FMS-1655M Part Number Guide BRAND LB = Johnson Controls UNIT FMS = Flow Monitor Station (FMS) SERIES 1655M = BACnet Monitor STYLE S = Surface mount T = Thin flush mount REMOTE SENSOR 01 = Standard remote sensor LIT-12013119...
  • Page 6 FMS-1655M System Precautions Warning Failure to follow the wiring diagrams could result in damage to your equipment and could void your warranty. Under no circumstances should a single transformer be split between actuator and controller. Doing so will damage the actuator, the transformer, the controller or all units.
  • Page 7 FMS-1655M System Precautions Red / 24 VAC / 30VA connected to the FMS Transformer 50/60 Hz Only Class 2 wiring in this compartment. Ground Blue 240 VAC 1 Amp Slow Blow 50/60 Hz Fuse 120 VAC 50/60 Hz Stepdown Isolation Transformer...
  • Page 8: Overview

    Audible button at the bottom of the adjoining corridor or anteroom. The front touchscreen display. port (P1) must be oriented towards the Key features of the FMS-1655M Monitor isolation room and the rear port (P2) include: The FMS-1655M Monitor provides a towards the corridor or anteroom.
  • Page 9: Mounting/Wiring

    FMS-1655M Mounting/Wiring 5. The FMS-1655M Monitor has a factory-calibrated analog output and is Installation available as voltage at the Vo terminal. The designated output (Vo) can be Remote sensor mounting used to control a damper actuator to procedure maintain a user set pressure setpoint when the FMS-1655M Monitor is used 1.
  • Page 10: Display Mounting Procedure (Surface Mount)

    FMS-1655M Display mounting procedure (surface mount) 1. Cut an opening in the wall adjacent to the door of the isolation room for installing the supplied single-gang “old work” low voltage mounting bracket (Figure 1) for the touchscreen display module. Nominal dimensions for the cutout are 3.65”...
  • Page 11: Flush Thin Mount Mounting Procedure

    If this is a at the 4-position terminal block CN3 retrofit application and existing drywall on the back side of the FMS-1655M is in place, then proceed with the next display, ensuring proper electrical step to prepare the opening for the connections.
  • Page 12: Installation Detail View

    Thin Silicone Caulking (apply around tube and Orange wall bracket between stainless steel to be installed plate and wall to seal unit first by using the penetration) To Johnson rotating clamps To FMS-1655M Controls isolation for secure wall Monitor transformer attachment. LIT-12013119...
  • Page 13 Note: To maintain sensor accuracy, Flow tube should not exceed 36 inches. Terminal For connection of transmitter to FMS-1655M Monitor. To FMS-1655M Monitor monitor Thin Silicone Caulking To Johnson Controls (apply around tube and isolation transformer Rotating clamps secure between stainless steel...
  • Page 14: Basic Programming

    FMS-1655M Monitor may be configured programming to start displaying the real-time differential pressure of the isolation room being After the FMS-1655M Monitor unit has monitored. been properly installed, apply power to the unit. Upon power up, the Safety Setting up alarm limits Halo™...
  • Page 15: Selecting Displayed Units

    System Setup menu. The user silent mode. If audible mode is selected, clock when the FMS-1655M Monitor is is prompted to sequentially enter the high a delay may be specified in seconds or connected to the BACnet network.
  • Page 16: Adding Password Security

    PID output setup individual passwords may be entered in the system, each with a specific access The FMS-1655M Monitor has an analog level. A password entry may be created output which can be used to control a by selecting the Passwords Setup option...
  • Page 17: Cleaning The Display

    Setup Menu if no password alarm. It automatically is stored. Otherwise, a reverts back to audible password must be entered mode when the alarm before the Main Setup condition is removed. Menu can be accessed. Hot-Spot Features of FMS-1655M Monitor Touchscreen Display LIT-12013119...
  • Page 18: Alarm Setpoints

    FMS-1655M Alarm setpoints LIT-12013119...
  • Page 19: Setup Menu Tree

    FMS-1655M Setup menu tree LIT-12013119...
  • Page 20 FMS-1655M LIT-12013119...
  • Page 21 Reserved Set to OFF ON = CMS-1655 Reserved Set to OFF ON = Enabled Mode Select OFF = FMS-1655M/ CMS-1655 ON = HMS-1655 Operational Mode: OFF = Demo Mode ON = Run Mode Pushbutton Switch (SW1): Reset Button Pushbutton Switch (SW2): Reserved BACnet®...
  • Page 22 FMS-1655M FMS-1655M Monitor wiring guide LIT-12013119...
  • Page 23 Branch Officies: Principal Cities World-wide Johnson Controls is registered trademark of Johnson Controls. ® All other marks herein are the marks of their respective owners. © Copyright 2019 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited. www.johnsoncontrols.com...