1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currently acquired
blinks.
Press
or
to make a recalibration of max. ± 5 °C. To save
the entry, set the DIP switch to OFF and press the DIP switch reset
button (also refer to Fig.
).
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON:
Setpoint limitation 16...35 °C
DIP switch OFF:
Setpoint limitation 3...35 °C
(factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON:
Temperature display in °C
DIP switch OFF:
Temperature display in °C
(factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
)
1.1.4 DIP switches 4 and 5
Optimum start control shifts switch on point P.1 such that the adjusted
setpoint will be reached at the required point in time. The setting
depends on the type of controlled system, that is, on heat transmission
(piping network, radiators), building dynamics (building mass,
insulation) and heat output (boiler output, flow temperature)
/ 1.1.6
(also refer to graph in Fig.
DIP switch 4 ON and 5 ON:
1 h/°C For slow controlled systems
DIP switch 4 ON and 5 OFF:
¼ h/°C For fast controlled systems
DIP switch 4 OFF and 5 ON:
½ h/°C For medium controlled systems
DIP switch 4 OFF and 5 OFF:
OFF
Off, no impact (factory setting)
Save the entry by pressing the DIP switch reset button.
Legend to graph in Fig.
/1.1.4
T
Temperature (°C)
t
Forward shift of switch on point (h)
TRx
Actual value of room temperature
Pon
Start point for optimum start control
1.1.5 Integral action time (volume adaptation):
DIP switches 6 and 7
DIP switch 6 ON and 7 ON:
Normally sized controlled systems, refer to factory setting.
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
press simultaneously
and
level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
settings by pressing
.
The expert level is quit by pressing the operating mode selection button
Code list
Function block
Code
00
Basic settings
01
10
LCD settings
11
12
30
Clock settings
31
32
Note 1: If the radio clock is not active or not present, this setting has no impact.
With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone).
CE1G2208xx
).
for 3 seconds, release
and keep
on display (also refer to Fig. G).
Name
Language
Sensor calibration
Illumination time
Background brightness
Contrast
Time zone
Deviation from time signal received from Frankfurt
(Central European Time CET) (refer to Note 1)
Start of summer time (refer to Note 2)
End of summer time (refer to Note 3)
DIP switch 6 ON and 7 OFF:
Fast controlled systems:
For small rooms, light radiators (plate radiators),
well insulated buildings or fan coils.
DIP switch 6 OFF and 7 ON:
Slow controlled systems:
For large rooms, heavy radiators (cast iron radiators),
poorly insulated buildings, or great building masses.
DIP switch 6 OFF and 7 OFF (factory setting):
Normally sized controlled systems:
For normal-size rooms, normally sized
radiators (steel tube radiators) and buildings with
average insulation.
Save the entry by pressing the DIP switch reset button.
1.1.6 Control gain (adaptation of heat output): DIP
switches 8 and 9
DIP switch 8 ON and 9 ON:
Normally sized heat output, refer to factory setting. DIP DIP
switch 8 ON and 9 OFF:
Undersized heat output:
For low boiler / flow temperatures, too small radiators
(surface) and too small volumetric flow
(nominal valve size).
DIP switch 8 OFF and 9 ON:
Oversized heat output:
For high boiler / flow temperatures, oversized radiators
(surface) and oversized volumetric flow (nominal
valve size).
DIP switch 8 OFF and 9 OFF (factory setting):
Normally sized heat output.
Save the entry by pressing the DIP switch reset button.
1.1.7 Radio clock: DIP switch 10
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.8 DIP switch reset
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
and
for 3 seconds, then release the buttons and, within 3 seconds,
depressed for another 3 seconds. This enables you to access the expert
.
Factory setting
English
off
10 seconds
0
0
0 hours
March 31 (31-03)
October 31 (31-10)
2015-02-27
quartz
Clock runs on built-in
Time signal DCF77 from Frankfurt
).
)
and
. Confirm the
Your setting
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL
7/50