Viessmann VITOFLEX 300-UF Operating Instructions Manual page 42

Fully automatic solid fuel boiler with grate combustion
Table of Contents

Advertisement

Maintenance
Inspection and maintenance
Activity
Boiler
Service electrical safety equipment
Service safety equipment on the water side
Pneumatic cleaning system
Check valves for tightness
Heat exchanger
B
Check system pressure at pressure gauge (minimum pressure,
water shortage)
Check thermally activated safety valve for tightness
Check gaskets on heat exchanger door
Combustion chamber
Check ash container connection for tightness
Check refractory lining for damage
Check refractory lining for slag deposits and remove slag where
necessary
Check flame temperature thermocouples for damage
Check gaskets of combustion chamber door and ash removal sys-
tem
Check intake aperture for secondary air
Check grate for damage
Check fire bricks of combustion chamber door for cracks
Ignition system
D
Check ignition pipe for blockages and clean if necessary
Service heating system
Compressor system (optional)
Note
If the compressor is operating continuously, this indicates that
there is a leak in the compressed air system. Check supply lines
and valves for leaks.
In the case of on-site supply of compressed air, ensure that the
compressor is suitable for continuous operation or can be pre-
vented from operating continuously.
After maintenance has been carried out
To reset maintenance, see page 24
42
(cont.)
A
C
Interval
300
1200
Every
hours
hours
six
months
O
O
O
O
O
Manufacturer's documentation
Annually
V
ZH
O
O
O
O
O
O
O
V
V
V