Viessmann VITOFLEX 300-UF Operating Instructions Manual page 27

Fully automatic solid fuel boiler with grate combustion
Table of Contents

Advertisement

"Fault" is displayed
No.
Fault message
017
Fault: Temperature level, hydraul-
ics, container X
018
Fault: Container X, cover closed
019
Fault: No container available
020
Fault: Changeover unit, time
monitoring
021
Fault: External charging
022
Fault: Thermal contact, boiler
pump
023
Fault: CO CO2
024
Fault: Electrostatic filter
025
Fault: Boiler flow sensor
026
Fault: Boiler return sensor
027
Fault: Contact sensor, feed
028
Fault: Boiler flue gas sensor
029
Fault: Cylinder sensor, top
030
Fault: Cylinder sensor, top centre
031
Fault: Cylinder sensor, centre
032
Fault: Cylinder sensor, bottom
centre
033
Fault: Cylinder sensor, bottom
034
Fault: Sensor f. weather-c. mode
035
Fault: System sensor
(cont.)
Cause
Loss of oil at the hydraulic unit
Pressure switch is incorrectly set
or faulty
Room temperature is too high
Material cover of container is not
in end position "open"
All containers are empty or in a
fault state
Changeover unit was running for
more than 5 minutes
External charging reports a fault
Electrical fault or motor overloa-
ded
No water or too little water in
the system
External detector reports CO or
CO2 emission into the boiler
room
Check possible cause at electro-
static filter control unit
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
Temperature sensor or test cable
is faulty
What to do if...
Remedy
Check the fittings, lines and cyl-
inders for leaks
Top up the oil
Replace pressure switch
Readjust setting for changeover
pressure at pressure switch
Reduce room temperature
Install oil cooler
Open container cover
Provide container with fuel
Check limit switch
Check the setting for the
changeover unit
Check and remedy the fault in ac-
cordance with message on charg-
ing controller
Check system pressure
Consult a qualified electrician
Immediately leave the boiler
room and ensure ventilation
Consult Viessmann Technical
Service
Check and remedy the fault in ac-
cordance with message on elec-
trostatic filter control unit
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
Consult a qualified electrician
27