5.2.1. Programming example

Load shedding configuration: LS
LS variable allows programming the timer associated shedding.
OUT-
Function
PUT
01 to n
LS
* In case the DTT variable configuration value is below the LS, value LS will be automatically set to the DTT value.
ATYS D10 / D20 - 542359B - SOCOMEC
function
fonction
temporisation associée
timer
Setting range
0 to 60 s (≤DTT)*
• Step 1: Press "right" push button to make
the first variable blink
• Step 2: press "up" and "down" to
modify the variable
• Step 3: Press "validate" to validate the
variable
• Step 4: Press "down" to access the nO
selection
Default values
2
EN
9