DIRIS Digiware
M-50
&
M-70
Gateway and Power supply interface
EN
www.socomec.com/operating-instructions_en.html

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DIRIS Digiware M-50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for socomec DIRIS Digiware M-50

  • Page 1 DIRIS Digiware M-50 & M-70 Gateway and Power supply interface www.socomec.com/operating-instructions_en.html...
  • Page 2: Table Of Contents

    7.1. Communication architectures ........7.2. DIRIS Digiware M-50/M-70 - wiring ....... .
  • Page 3 15. ANNEX A SNMP COMMUNICATION WITH THE DIRIS DIGIWARE M-50 / M-70 ....15.1. SNMP generalities ..........
  • Page 4: Documentation

    1. DOCUMENTATION All documentation on DIRIS Digiware M-50 and M-70 is available on the SOCOMEC website: www.socomec.com/operating-instructions_en.html DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 5: Hazards And Warnings

    • The auxiliary power supply voltage indicated on the device is observed: 24 VDC ± 10%. • A SOCOMEC 230 VAC / 24 VDC power supply unit (P15 ref. 4829 0120) or a 24 VDC max 20 W class 2 power supply unit / SELV is used.
  • Page 6: Responsibility

    • Any cable which needs to be replaced may only be replaced with a cable having the correct rating. • Despite constantly striving for quality in preparing this manual, errors or omissions are always a possibility and are not the responsibility of SOCOMEC. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 7: Preliminary Operations

    • The device has not been damaged during transportation. • The device reference number conforms to your order. • The packaging includes the device fitted with removable terminal blocks and a Quick start guide. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 8: Cyber Security Recommendations And Best Practices

    4. CYBER SECURITY RECOMMENDATIONS AND BEST PRACTICES* The DIRIS Digiware M-50/M-70, as any device connected to a user’s Ethernet network, must be protected against any risk of cyber-attack or data loss/destruction. (*) Our M-50/M-70 gateways provide certain cyber security features to prevent these attacks and to help users in their responsibility to implement and guarantee adequate IT protection.
  • Page 9 Multiple profiles are available to access the web application. The highest profile is “Cybersecurity”, which allows you to manage users’ access to the web application based on what is relevant for them. Profiles are password protected. Certain measures are taken into account in Socomec M-50/M-70 gateways to reduce the risk of password theft:...
  • Page 10: Introduction

    SNMP v1, v2, v3 & Traps SNMP v1, v2, v3 & Traps FTP(S), SMTP(S), SNTP, HTTP(S), FTP(S), SMTP(S), SNTP, HTTP(S), Other services DHCP DHCP WEBVIEW-M Power & Energy Webserver WEB-CONFIG Monitoring software DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 11: Introduction To Diris Digiware M

    These products may be connected by a Digiware bus and/or an RS485 bus. 5.2.1. Introduction to DIRIS Digiware M-50 The DIRIS Digiware M-50 gateway is a master device on the RS485 bus and master on the DIRIS Digiware bus. It is used as an Ethernet gateway.
  • Page 12: Introduction To Diris Digiware

    The logs are then Specific configuration (data is recorded Load curves are then automatically automatically). automatically downloaded downloaded from the from the meter’s cache meter’s cache memory memory to the M-70. to the M-70. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 13: Front Leds

    - OFF: no communication. - Flashing: communication in progress on the RS485 and/or Digiware bus. BLUETOOTH - OFF: Bluetooth is deactivated - ON: Bluetooth is activated - Flashing: On-going pairing process DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 14: Dimensions (In/Mm)

    Refer to the safety instructions (section “2. Hazards and warnings”, page 5) 6.2. DIN rail mounting 1.38 0.29 or 0.59 7,5 or 15 DIN rail mounting with access to front face only DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 15: System Wiring

    7. SYSTEM WIRING Only use a SOCOMEC Digiware bus cable (UTP RJ45 straight, twisted pair, unshielded, AWG 24, 600V CAT V -10 ... +70°C). When wiring, make sure you separate the low voltage (LV) section and the very low voltage (SELV) section to prevent any risk of electric shock.
  • Page 16: Communication Architectures

    DIRIS Digiware M-50/M-70 RS485 (*) If the 24 VDC power supply is not provided by Socomec, a 1 A / 24 VDC fuse must be used. For North America, the use of recognized fuses is mandatory. When configured as RS485 Master, the M-50/M-70 acts as a gateway (Digiware to Ethernet and RS485 to Ethernet).
  • Page 17: Automatic Detection Of Devices

    - FAST (default mode): this mode will only detect DIRIS Digiware modules on the Digiware bus and RS485 bus, DIRIS B and DIRIS A-40 on the RS485 bus. - FULL: this mode will also detect other Socomec PMDs (DIRIS A) and meters (COUNTIS E) connected on the RS485 bus.
  • Page 18 4a/5a. Press the front button on each slave device that has a fixed COM LED, for at least 2 seconds. 4b/5b. COM LEDs of the modules start blinking again. 6. COM LED of the M-xx gateway starts blinking again, and slave devices can now communicate with the M-xx gateway. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 19: Webserver Embedded In The M-50/M-70 Gateways

    (WEBVIEW-M, M-70 only). To connect to the gateway’s webserver, enter its IP address in the address bar of your web browser. Default Ethernet parameters of the DIRIS Digiware M-50/M-70 gateways are as follows: - IP address: 192.168.0.4 - Mask: 255.255.255.0 - Gateway: 192.168.0.1...
  • Page 20 Account lockout policy: 3 unsuccessful login attempts to the Admin, Advanced User or Cyber security account will lock it for 1 hour. If you do not wish to wait 1 hour, you can reboot the M-50/M-70 gateway. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 21: Admin Profile

    If you have forgotten to save the passphrase, the only option left is to reset the M-50/M-70 to factory default settings. 10.2. Admin profile When connected as Admin, you can access the configuration page by clicking on the “wrench/screwdriver” icon on the top left corner: DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 22: Devices" Tab

    • Go to the “Devices” tab: • Click on “Modify active configuration” (1), and then click on “Sources” (2): • Click on the “AutoDetect” icon on the right bottom corner to detect and add SOCOMEC devices already present in the M-50/M-70 gateway’s topology.
  • Page 23 • Click on the “+” icon at the right bottom corner for manually adding products one at a time. Adding a M-50/M-70 gateway or D-50/D-70 display will add the entire topology under that gateway or display. • The various SOCOMEC devices that are supported by WEBVIEW-M are given in the following list: Gateways...
  • Page 24: Protocols" Tab

    Management System, etc.) can be configured from the “Protocols” tab. • Network Configuration This tab allows you to modify the gateway’s IP configuration: After modifying those parameters, a reboot of the M-50/M-70 gateway is necessary. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 25 File format: data can be exported in different file formats (CSV and EMS – see appendices 1 and 2). The CSV format is easier to use while EMS is better for importing data into an external energy management software. o Test connectivity: Test the FTP export function DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 26 Refer to ANNEX. A and B for more information on BACnet and SNMP communication protocols with the M-50/M-70 gateway. - Time: allows you to configure an SNTP server to automatically synchronise the clock of the M-50/M-70 gateway to an external computer. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 27 Email sender address: email address used by the M-50/M-70 gateway to send emails o Email destination address 1: email address #1 to send email notifications to o Email destination address 2: email address #2 to send email notifications to DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 28: Cyber Security Profile

    - Secure the client-server communication (HTTPS, FTPS, SMTPS). - Prevent denial-of-service attacks by implementing a firewall in the M-50/M-70 gateway. The configuration of Cyber security functions is explained in paragraphs 10.3.1 through 10.3.4. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 29: Security Policy" Tab

    10.3.2. “Security Policy” tab DIRIS Digiware M-50/M-70 gateways can reduce the attack exposure by disabling certain peripherals or services that are not essential to the customer’s use case. Peripherals - USB: disable the USB port of the M-50/M-70 gateway. - Bluetooth Low Energy: disable the Bluetooth Low Energy of the M-50/M-70 gateway.
  • Page 30: Https" Tab

    This tab allows you to secure the client (M-50/M-70) to server (FTPS, SMTPS) communication by adding the relevant Certificate Authorities (CA) on the Client side. Several common Certificate Authorities are already included to the M-50/M-70 gateway, but the user can add others if necessary. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 31: Firewall" Tab

    This tab allows you to implement a firewall to protect against Denial-Of-Service attacks also called Flooding attacks by entering a max bandwidth in kbit/s and a max number of requests per second: A client exceeding one of the above parameters while communicating to the DIRIS Digiware M-50/M-70 gateway will be blocked for 30 seconds.
  • Page 32 Upload the desired firmware package (.dfu file) by clicking on the “Browse” button. Wait until the package is loaded, and once package consistency check I finished, click on “Upgrade”: Once the upgrade is finished, the web page will reload automatically: DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 33: Webview-M

    10.4. WEBVIEW-M For more information on the visualisation of measurement data, please refer to the WEBVIEW-M instruction manual, available on the Socomec website at the following link: www.socomec.com/operating-instructions/en/software-solution DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 34: Configuration Via Easy Config System

    The EasyConfig System software can be downloaded from the Socomec website at the following link: https://www.socomec.com/easy-config-software_en.html The Configuration of the DIRIS Digiware M-50/M-70 gateway and downstream Socomec devices can be done from the EasyConfig System software, by connecting a computer to the M-50/M-70 gateway either via USB or via Ethernet.
  • Page 35 “Organisation” part, next to the M-50/M-70 gateway. > Configuration of slave devices can be done directly without unplugging the USB cable, by clicking on the Wrench icon on the left side bar: DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 36: Ethernet Connection Mode

    “Organisation” part, next to the M-50/M-70 gateway. > Configuration of slave devices can be done directly by clicking on the Wrench icon on the left side bar and selecting the right device: DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 37 DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 38: Alarms

    DIRIS Digiware M-50 and M-70 gateways collect alarms from downstream devices connected on the Digiware or RS485 bus. DIRIS Digiware M-50 and M-70 gateways also support 7 System alarms. The types of system alarms and the possible causes are listed in the table below:...
  • Page 39: Step Commissioning Checklist For Your Digiware System

    Why is the ALARM LED on the M-50/M-70 flashing ? - If this is the first time you are using the DIRIS Digiware M-50/M-70 gateway, it could be that the default passwords for the Advanced User, Admin and Cyber security profiles have not been changed yet. The “Password Alert”...
  • Page 40: Diris Digiware M-50/M-70 Technical Characteristics

    - Product storage: 1 year of full time battery back-up (based on an average storage temperature of 25°C). - Product life: 10 days / year of battery back-up over 9 years. Battery type 3V Lithium cell battery, 48mAh rated capacity. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 41: Environmental Characteristics

    Conducted RF immunity IEC 61000-4-6 Power magnetic field immunity IEC 61000-4-8 IV, 400A/m Dips immunity IEC 61000-4-11 Conducted emissions CISPR11 Radiated emissions CISPR11 Passed Gr:1 – Class B Electromagnetic environment Industrial + Residential DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 42: Annex A

    IP networks. It works in a client-server communication mode on an Ethernet physical layer. The DIRIS Digiware M-50 / M-70 supports SNMP v1, v2 and v3.The M-50 / M-70 is an agent SNMP v1, v2, v3 which responds to queries from managers (also called management stations or supervisors).
  • Page 43: Snmp Versions Supported

    Both passwords have to be entered in the Agent (DIRIS Digiware M-50 / M-70) and the Manager and must be identical. A matching Read Community allows the Get functions to be executed on the agent.
  • Page 44: Snmp Ports

    U-30 I-30 I-30 15.5. Retrieving data using the DIRIS Digiware M-50 / M-70 MIB file The DIRIS Digiware M-50 / M-70 is compliant with MIB-II defined by the MIB standard RFC 1213 which defines the following structure: Root iso (1)
  • Page 45 Entry (always = 1) Service ID 10000 This OID is associated with the multiple devices connected downstream the DIRIS Digiware M-50 / M-70. To identify those multiple devices, the Modbus address and the load number are added to the end of the OID.
  • Page 46: Snmp Configuration Via Easyconfig System

    15.6. SNMP configuration via EasyConfig System After logging in to EasyConfig System on the DIRIS Digiware M-50 / M-70, you can find the SNMP settings in the SNMP menu, under SNMP settings: • Community configuration SNMP V1 & V2: SNMP V1 Read Community: Read-only community string for SNMP v1. Default community string is “public”. It allows a manager to retrieve read-only data from a device connected to the DIRIS Digiware M-50 / M-70.
  • Page 47: Snmp Configuration Via The Embedded Webserver

    Click on the “Wrench” icon on the top left corner and click on “Protocols”: Click on the “Field protocols” tab, and under “Communication”, scroll down to the SNMP part to enter SNMP V1/V2 or V3 settings, as well as Trap notifications: DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 48: Annex B

    It acts as a BACnet IP gateway to all devices compatible and connected downstream via RS485 or the Digiware Bus. The PICS (Protocol Implementation Conformance Statement) of the DIRIS Digiware M-50 / M-70 is available on the Socomec website at www.socomec.com.
  • Page 49 • Proprietary. Vendors can add their own created properties. Device Object: Every BACnet device compatible with the DIRIS Digiware M-50 / M-70 must have the Device Object and its associated required properties that fully describe the BACnet device to the network.
  • Page 50 • The device with OID (1xx) is the device with the Modbus address xx. Analog Input Object: The DIRIS Digiware M-50 / M-70 acts as a BACnet gateway. It provides a number of Analog Input objects which may be available from the devices compatible and connected to the DIRIS Digiware M-50 / M-70.
  • Page 51 • with MM = Index of the measurement type (see Analog Input Measurement List). For example, Analog Input with OID 204 reflects Phasis/Neutral Voltage V1 of Load 2 of corresponding device. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 52 P2 Active Power W Signed • • • • • PowerActiveP3 P3 Active Power W Signed • • • • • PowerRActiveQ1 Q1 Reactive Signed • • • • • Power DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 53 Positive Reactive VArh Unsigned • • • • Energy Negative VArh Unsigned • • • • Reactive Energy Apparent Energy VAh Unsigned • • • Multifluid feeder Signed • • • DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 54: Bacnet Services

    The PICS file (Protocol Implementation Conformance Statement) is available at www.socomec.com After logging in to Easy Config System on the DIRIS Digiware M-50 / M-70, you can find the BACnet IP settings in the BACnet menu under BACnet settings: Activation: Enable or disable the BACnet IP function Main instance ID: 100 by default.
  • Page 55: Bacnet Configuration From The Embedded Webserver

    Virtual Network ID: set the virtual Network ID of the M-50/M-70 gateway. It must be unique within the BACnet network. Main instance ID: set the main Instance ID (100 by default) for the M-50/M-070 gateway. It must be unique within the BACnet network. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 56: Annex C

    Authentication part: Site Name & Server Name: used to identify from which DIRIS Digiware M-50/M-70 the files are being exported. The default site name is “SITE” (must be modified if the exoirt mode is set to EMS) et the default server name corresponds to the NET ID marked on the front face of the M-50/M-70 gateway.
  • Page 57 August 15th, 2017 at 20:00 (8:00pm), it contains Load curves (Demand Power) from a device named I35 from a gateway whose Server name is GTWDEF and Site name is socomec. In EMS mode, the Site Name must be different from default name (“SITE”), or the “FTP error” system alarm will be triggered.
  • Page 58: Ftp Planning Configuration

    Load curves / demand: P, Q, S etc. (Load curves) For each data type, specify the rate at which data will be exported (once an hour, once a day etc.) and at which time. DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC...
  • Page 59: Understanding The Exported .Csv File In Ems Mode

    Key in column “B”, part (1) as a unique import code and do not only use the simplified index key in column “A”, part (2). If multiple DIRIS Digiware M-50/M-70 gateways are exporting to the same folder, the simplified index key cannot differentiate them.
  • Page 60 CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE 67235 BENFELD, FRANCE www.socomec.com 548751B...