INSTRUCTIONS - ELECTRICINEMA
Type A, B & C. Connect IP Projection Screen including IP Protocol
SETTING THE PARTIAL POSITIONS
Note: Partial positions are set using internal timers, position can vary due to mains voltage
fluctuations, motor load changes and temperature.
COMMAND
MAF ADDRESS + 16
44
Unified Address
45
Unified Address
To set Partial 1 – stop screen at required location and send command - if screen 1 is being used
IP address 192.168.0.32:3002 – command 044 17 using unified address would see the
screen set partial position 1
To set Partial 2 – stop screen at required location and send command - if screen 1 is being
used a IP address 192.168.0.32:3002 – command 045 17 using unified address would see the
screen set partial position 1
17. MODULE STATUS FEEDBACK
A module status buffer (20 record FIFO) is updated as a automatically generated Send
Register Commands with register number = 0x20 are sent from each module.
The module status buffer contains the Module ID (1 byte), and Module Status (2 bytes)
COMMAND
050
Response from module e.g. 150, 1, 1, 6 – value 6 indicates screen at top
COMMAND
VALUE 1
150
Status
Note – Status=1 is returned if valid data and no further records in the status buffer
Status=2 is returned if valid data and there are still records in status buffer
Status=3 is returned if valid data but the buffer is full (eg may have lost data)
Status=6 is returned if there are no new records
This buffer is updated when screens are moved. It is also updated automatically every 60 seconds.
It needs to be polled regularly to clear the stored data otherwise it will get full and records will be
lost. Even though screens may not be moving the data is being updated even though the status is the
same.
VALUE 1
DESCRIPTION
3781
Sets Partial Position 1
3781
Sets Partial Position 2
VALUE 2
VALUE 3
Module ID
Module Status Register (0x20)
RESPONSE TYPE NO
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Example of string from module:
192.168.0.32 3001 Up Send 30 1
192.168.0.32 3001 Up Receive 130, 1, 1
192.168.0.32 3001 Status Change Receive 9999
192.168.0.32 3001 Get Module Status Send 67 3781
192.168.0.32 3001 Get Module Status Receive 167, 0, 255, 255, 255, 255, 255, 255, 255, 255
192.168.0.32 3001 Status Change Receive 9999
192.168.0.32 3001 Get Module Status Send 67 3781
192.168.0.32 3001 Get Module Status Receive 167, 6, 255, 255, 255, 255, 255, 255, 255, 255
CONNECT IP MODULE
Moving top
Moving bot
Moving PP1
Moving PP2
Moving PPT
Moving PPB
At TOP
At BOTTOM
At PP1
At PP2
Stopped manual
Error
Spare
Fail-timeout
Fail – current
Rattle
At PPT
At PPB
Continued Over.../