2. Performance Specifications

The performance specifications for Network Modules are indicated as follows.
(1) A1SJ72QLP25
Item
Maximum link
X/Y
points per
B
network
W
Maximum link points per
station
Maximum number of I/O
points per remote I/O station
Communication speed
Communication method
Synchronization method
Encoding method
Transmission route format
Transmission format
Maximum number of networks 239
Number of stations for
connection per network
Overall distance
Station-to-station distance *1
Error control method
RAS function
Transient transmission
Connection cable
Applicable connector
5VDC current consumption
Weight
*1: The distance between stations is restricted in accordance with the type of cable and number
of stations. Refer to Reference Manual of master module in use for details.
*2: Specialised training and specific tools are required to connect the connector to the
optical-fiber cable; the connector itself is a custom product. Please contact your nearest
Mitsubishi Electric System Service Corporation when purchasing these items.
For general specifications of the network module, refer to the user's manual for the PLC CPU
that is to be used.
8192 points
8192 points
8192 points
Remote master station
Y+B
+ (2 W)
8
Remote I/O station
X +B
+ (2 W)
8
Remote master station
Remote sub-master station
Y+B
+ (2 W)
8
X+Y<1024 (main base unit + 1 extension base units)
When X and Y overlap, either of them becomes effective.
10Mbps (equivalent to 20Mbps for multiple transmission)
Token ring
Frame synchronization
NRZI encoding (Non Return to Zero Inverted)
Duplex optical loop
Conform to HDLC (frame format)
65 stations (Remote master station: 1 Remote I/O stations: 64)
30km
SI optical cable
H-PCF optical cable
Broad-band H-PCF optical cable : 1km
QSI optical cable
16
12
Retry by CRC (X
+X
Loop back function due to abnormality detection and cable
disconnection
Diagnostic function for local link circuit check
Abnormality detection by link special relay, resistor
Network monitor, each type of diagnostic function
Monitoring with peripheral device, program up/download
Optical fiber cable (Arranged by user *2)
2-core optical connector plug (Arranged by user *2)
0.52A
0.41kg
2
Specifications
A1SJ72QLP25
remote I/O station
<1600 bytes
remote master station
<1600 bytes
remote sub-master station
remote master station
<2000 bytes
: 500m
: 1km
: 1km
5
+X
+1) and overtime