[Flow of function selection]
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room
temperature detection position is given.
For actual operations, refer to steps 1 to 0.
Mode number
F
E
G
Selecting functions using the wired remote controller
1 Check the function selection setting.
2 Switch to function setting mode.
(Press A and B at the same time
with the remote controller stopped.)
3 Specify refrigerant address 00 (outdoor unit)
4 Specify unit No. 00. (indoor unit)
(Use C and D.)
6 Select mode No. 02
(room temperature detection position).
7 Select setting No. 03 (remote controller fixed).
(Use F and G.)
0 Function selection end screen
(Press A and B at the same time.)
Setting number
Refrigerant address
C
(Specified indoor unit:
5 Enter the setting.
BLOW operation)
(Press E.)
Example:
8 Enter the setting.
Selecting room temperature
(Press E.)
detection position
NO
Finished
YES
The above procedure must be carried out only if changes are necessary.
Unit number
I
A
B
J
D
For modes 15 and higher,
press J and B at the same time.
NO
Modes 01 to 13 can be activated
by pressing buttons A and B
simultaneously, and modes 15 to
28 by pressing buttons B and J.
YES
Change refrigerant
address unit No.
9
43