4.2.2 Master Format
Device Address
Device address – 1 byte field ranging from 1 to 247. Broadcast address 0
Function code – 1 byte field with a value range 1-127 representing the standard or extended
function code
Data payload –
0-N bytes with response data from the device. Error response will be a 1 byte
value 1-255.
CRC –
2 bytes computed mathematically
4.2.3 Slave Response Format
Device Address
Device Address – Echo of device address sent in master message to the device
Function code – Echo of function code sent in master message to the device
Data payload –
0-N bytes with response from device.
CRC-
2 bytes with a value computed mathematically
4.2.4 Standard Message Format
Read Holding Registers is used to retrieve measurements
Message
Address
1 byte
Function Code
1 byte
Data Address
2 bytes
Register Count
2 bytes
CRC
2 bytes
*Byte count = 2*Register Count
Write Single Register is used to configure instrument settings
To set a single register in a device:
Message
Address
1 byte
Function Code
1 byte
Data Address
2 bytes
Register Count
2 bytes
CRC
2 bytes
Unidata Manual - 6527B and 6537A Starflow QSD User Manual 17 01 2020.docx
Manual – Starflow QSD Model 6527B and 6537A
Function Code
Function Code
1-247
0x03
0 to 0xFFFF
1-247
0x06
0 to 0xFFFF
0 to 0xFFFF
Data Payload
Data Payload
Response
Address
Function Code
Byte Count
Data Payload
CRC
Response
Address
Function Code
Byte Count
Data Payload
CRC
CRC
CRC
1 byte
1-247
1 byte
0x03
1 byte
N bytes
2 bytes
1 byte
1-247
1 byte
0x06
1 byte
0 to 0xFFFF
N bytes
0 to 0xFFFF
2 bytes
Page 13