Walk Test Mode - echoflex MOS-21 Series Installation Manual

Wireless motion sensor for occupancy / vacancy detection with integrated diagnostic tools
Table of Contents

Advertisement

Note:
• Range Confirmation is only available with "F series" or later Echoflex
Controllers.
• The MOS must be at full charge and/or have the battery installed for Range
Confirmation Tests energy requirements.
• Only one receiver can be linked to the sensor for proper operation of the test.
• Disable repeaters in range for proper test operation.
All three LED's will blink (for 1 second) in this test mode when the sensor
transmits or receives a Range Confirmation Telegram followed by the sensor
displaying the linked signal strength status for 2.5 seconds, see table below.
The test will repeat every 10 seconds and run for a duration of 3 minutes. You
may quit the test at any time by pressing the test button for 6 seconds.

Walk Test Mode

Walk test mode allows the installer to verify areas that are within range of the
motion sensor.
1. To enter walk test mode, press and hold the teach button until the green
LED begins to blink (about 6 seconds).
2. A quick press and release of the button at this point will allow you to select
between test modes. Pressing and releasing the test button scrolls through
the LED indicators. When the red LED is blinking, go to step 3.
3. Press and hold the test button again for 6 seconds to select walk test.
The red LED will blink every time a motion sensor trigger is detected. The test
times out in 100 seconds. If a faster exit from walk test mode is required, press
and hold the teach button for 10 seconds.
Sensitivity Adjust Mode
The sensitivity adjust mode allows the user to change the PIR sensitivity. False
occupancy states caused by other elements can be reduced by selecting the
minimum sensitivity level. The default setting is high sensitivity.
1. To enter sensitivity adjust mode, press and hold the teach button until the
green LED begins to blink (about 6 seconds).
2. A quick press and release of the button at this point will allow you to select
between test modes. Pressing and releasing the test button scrolls through
the LED indicators. When the red and amber LEDs are blinking, go to step 3.
3. Press and hold the test button again for 6 seconds to select sensitivity
adjust mode.
A press and release of the button will allow you to scroll through the settings as
shown in the table below.
6
LED
Green - Solid 2.5 sec
Amber - Solid 2.5 sec -70 to -80 dBm
Red - Solid 2.5 sec
No LED
Signal Strength
-41 to -70 dBm
-80 to -95 dBm
No linked receivers detected

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mos-21uaMos-21ubMos-21ucMos-21caMos-21cbMos-21cc ... Show all

Table of Contents