EBARA DDLFU Operating Instructions, Installation & Maintenance Manual page 4

Submersible dry pit non-clog water/wastewater pump

Advertisement

EBARA Submersible Sewage Pumps
Instruction Manual
Installation
2. Pump Installation
When lifting the pump, use appropriate crane (or hoist) and lift system, check position and tightness of lift system
so that weight of the pump is not UNBALANCED.
Failure to observe this precaution can result in serious accidents.
Handle the cables very carefully. If they are bent or pulled excessively, the cable and the moulded seal may be
damaged, resulting in insulation failure. Also, care is needed to protect cable ends against water intrusion.
Before installation check rotation. Correct rotation is clockwise when viewed from top of motor. Read ELECTRICAL WIRING.
1. Clean the installation area.
2. Under no circumstances should the cable be pulled
while the pump is being transported or installed. Attach
a chain or rope to the grip and install the pump.
3. This pump must not be installed on its side. Ensure
that it is installed upright on a secure base.
4. Install piping so that air will not be entrapped. If piping
must be installed in such a way that air pockets are
unavoidable, install an air release valve wherever such
air pockets are most likely to develop.
5. Do no operate the pump for a long time with the water
level near the minimum operating level as the automatic
cut-off switch incorporated inside the motor will be
activated. To avoid dry operation, install an automatic
operating system, as shown in Fig. 1 and maintain a
safe operating water level.