Troubleshooting - ABB RELION 615 Series Protocol Manual

Iec 60870-5-103 communication protocol
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS759001 A
3.7
Table 13:

Troubleshooting

Condition
Cause
Slow or no update of
Protocol data is available for active IED applications
data, reports disabled
and the IED system. Active IED applications mean the
function blocks that have been added into the
protection relay's configuration using Application
Configuration in PCM600. The IED system data is
always available and is not dependent on the
application configuration.
A protection relay variant has a standard application
configuration that has been done in advance. This
configuration can be modified with PCM600. It is also
possible to start a completely new configuration from an
emptied configuration state in Application
Configuration. When a new IED configuration is created
from an empty configuration state, an additional
PCM600 check must be done at the end.
615 series
Communication Protocol Manual
Troubleshooting
Vendor-specific implementation
Remedy
Select manually the check boxes for clients of all visible
61850 data sets in the IEC 61850 Configuration tool,
see the engineering guide for detailed instructions. This
procedure enables reporting for the data sets, and
report control blocks should appear on the Report
Control tab.
Section 3
31