Basic defrost controller

Advertisement

Quick Links

Penn | TC3B22 | Installation Guide Rev. C | Part No. 24-7664-03566 | Page 1 of 2 | 19 January 2021
Basic Defrost Controller Installation Guide
TC3B22
Basic controller for refrigerated cabinets, with energy-saving strategies
E
ENGLISH
-
Controller for normal and low temperature units
-
Power supply for TC3B22N5x: 115 VAC
-
Power supply for TC3B22N7x: 230 VAC
-
Cabinet probe and auxiliary probe with a negative temperature coefficient (NTC)
-
Door switch or multi-purpose input
-
Cooling or heating operation
1
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). Fit the controller to a panel with the snap-in brackets supplied.
INSTALLATION PRECAUTIONS
-
Ensure that the thickness of the panel is between 0.8 mm and 2.0 mm (1/32 and 1/16
in)
-
Ensure that the working conditions are within the limits stated in TECHNICAL
SPECIFICATIONS.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
-
In compliance with safety regulations, install the device correctly to ensure adequate
protection from contact with electrical parts. Fix all protective parts in such a way so
as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference, connect the power cables as far away
as possible from the signal cables.
-
Power supply for TC3B22N5x: 115 VAC.
-
Power supply for TC3B22N7x: 230 VAC.
PRECAUTIONS FOR ELECTRICAL CONNECTION
If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
-
0.5 N•m (4 in. lb).
If you move the device from a cold to a warm place, the humidity may cause
-
condensation to form inside. Wait an hour before you switch on the power.
Make sure that the supply voltage, electrical frequency, and power are within the set
-
limits. See TECHNICAL SPECIFICATIONS.
Disconnect the power supply before you do any type of maintenance.
-
Do not use the device as safety device.
-
For repairs and further information, contact the Penn sales network.
-
3
FIRST-TIME
1.
Follow the instructions in MEASUREMENTS AND INSTALLATION to install the controller.
2.
Power up the device as shown in ELECTRICAL CONNECTION and an internal test runs.
The test normally takes a few seconds. When it finishes the display switches off.
3.
Configure the device as shown in Table 6.1 in SETTINGS.
For recommended configuration parameters for first-time use, see the following table.
PAR.
DEF.
PARAMETER
32
SP
Setpoint
P2
1
Temperature unit of measurement
d1
0
Defrost type
Check that the remaining settings are appropriate; see CONFIGURATION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in ELECTRICAL CONNECTION without powering
up the device.
6.
Power up the device.
4
USER INTERFACE AND MAIN FUNCTIONS
4.1
Switching the device on or off
1.
If POF = 1, tap the ON/STAND-BY key for 4 s.
If the device is switched on, the display shows the P5 value, cabinet temperature by default. If
the display shows an alarm code, see ALARMS.
LED
ON
Compressor on
Defrost or pre-dripping
active
Evaporator fan on
- Alarm active
AUX
- Cabinet light on by
key
- If device on, energy
saving active
- If device off, low
consumption active
View temperature
°C/°F
Device off
If 30 s have elapse and you do not press the keys, the display shows the "Loc" label and the
keypad locks automatically.
4.2
Unlocking the keypad
Tap any key for 1 s. The display shows the label "UnL".
4.3
Setting the setpoint
Check that the keypad is not locked.
1.
2.
3.
4.4
Activating manual defrost (if r5 = 0, default)
Check that the keypad is not locked.
1.
If P4 = 1 (default), the defrost activates if the evaporator temperature is lower than the d2
threshold.
4.5
Turning the cabinet light on or off (if u0 = 3)
1.
5
ADDITIONAL FUNCTIONS
5.1
Navigating the additional functions menu
Before you begin, check that the keypad is not locked.
1.
2.
3.
4.
5.
6.
5.2
Additional functions menu
Use the additional functions menu to cycle through the labels in the following table.
LABEL
VALUE
CH
rCH
149
Pb1
Pb2
6
SETTINGS
6.1
Setting configuration parameters
1.
2.
3.
4.
5.
6.
7.
8.
9.
MIN. - MAX.
r1 to r2
0 = °C
1 = °F
6.2
Restoring the default factory settings and storing customized settings as
0 = Electric
1 = Hot gas
default
2 = Compressor stopped
Important
- Check that the factory settings are appropriate; see CONFIGURATION
PARAMETERS.
- When you store customized settings, you overwrite the default.
1.
2.
3.
VAL.
149
161
4.
5.
6.
7.
8.
Interrupt the power supply to the device.
9.
OFF
FLASHING
Compressor off
- Compressor protection active
- Setpoint setting active
-
- Defrost delay active
- Dripping active
Evaporator fan off
Evaporator fan stop active
-
Cabinet light on by digital input
-
-
-
-
Device on
Device on or off active
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the value within the
limits r1 and r2.
Tap the SET key or do not operate for 15 s.
Tap the UP key for 2 s.
Tap the ON/STAND-BY key.
To access the additional functions menu, tap the DOWN key for
4 s.
To navigate to a label, tap the UP or DOWN key within 15 s.
To select a label, tap the SET key.
If you cannot edit the parameter, the value displays.
If you can edit the parameter, tap the UP or DOWN key to
navigate to the value that you want.
To set the parameter value, tap the SET key.
To exit the procedure, tap the ON/STAND-BY key, or do not
operate the controller for 60 s.
DESCRIPTION
View compressor functioning hours in hundreds
Delete compressor functioning hours
Command to delete compressor functioning hours
Cabinet temperature
Auxiliary temperature
Tap the SET key for 4 s. The display shows the label "PA".
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the password.
Tap the SET key or do not operate for 15 s. The display shows
the label "SP".
Tap the UP or DOWN key to select a parameter.
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the value.
Tap the SET key or do not operate for 15 s.
Tap the SET key for 4 s, or do not operate for 60 s, to exit the
procedure.
Tap the SET key for 4 s. The display shows the label "PA".
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the value.
DESCRIPTION
Restores the default factory settings
Stores customized settings as default
Tap the SET key or do not operate for 15 s. The display shows
the label "dEF" when you set the value "149" or the label "MAP"
when you set the value "161".
Tap the SET key.
Tap the UP or DOWN key within 15 s to set "4".
Tap the SET key or do not operate for 15 s. The display shows
"- - -" flashing for 4 s, then the device exits the procedure.
Tap the SET key 2 s before step 6. to exit the procedure
beforehand.
7
CONFIGURATION PARAMETERS
PAR.
DEF.
SETPOINT
SP
32
Setpoint
PAR.
DEF.
ANALOG INPUTS
0
CA1
Cabinet probe offset
CA2
0
Auxiliary probe offset
P0
1
Probe type
P1
1
Enable °C decimal point
P2
1
Temperature unit of measurement
P4
1
Auxiliary probe function
P5
0
Value displayed
P8
5
Display refresh time
PAR.
DEF.
CONTROL
r0
4
Setpoint differential
r1
-50
Minimum setpoint
r2
100
Maximum setpoint
r4
0
Setpoint offset in energy saving
r5
0
Cooling or heating operation
r12
1
Position of the r0 differential
PAR.
DEF.
COMPRESSOR
0
C0
Compressor on delay after power-on
C2
3
Compressor off minimum time
C3
0
Compressor on minimum time
C4
0
Compressor off time during cabinet
probe alarm
C5
10
Compressor on time during cabinet
probe alarm
176
C6
Threshold for high condenser
temperature warning
C7
194
Threshold for high condenser
temperature alarm
C8
1
High condenser temperature alarm
delay
PAR.
DEF.
DEFROST (if r5 = 0)
d0
8
Automatic defrost interval
d1
0
Defrost type
d2
46
Threshold for defrost end
d3
30
Defrost duration
d4
0
Enable defrost at power-on
d5
0
Defrost delay after power-on
1
d6
Value displayed during defrost
2
d7
Dripping time
d8
0
Defrost interval counting mode
d9
32
Evaporation threshold for automatic
defrost interval counting
0
d11
Enable defrost timeout alarm
d15
0
Compressor on consecutive time for
hot gas defrost
d18
40
Adaptive defrost interval
d19
6
Threshold for adaptive defrost,
relative to optimal evaporation
temperature
d20
180
Compressor on consecutive time for
defrost
d22
-4
Evaporation threshold for adaptive
defrost interval counting, relative to
optimal evaporation temperature
PAR.
DEF.
ALARMS
A1
-20
Threshold for low temperature alarm
(relative to setpoint)
A4
20
Threshold for high temperature
alarm (relative to setpoint)
A6
12
High temperature alarm delay after
power-on
A7
15
High and low temperature alarms
delay
A8
15
High temperature alarm delay after
defrost
A9
15
High temperature alarm delay after
door closing
A11
4
High and low temperature alarms
reset differential
PAR.
DEF.
FANS
F0
3
Evaporator fan mode during normal
operation
F1
30
Threshold for evaporator fan
operation
F2
0
Evaporator fan mode during defrost
and dripping
F3
2
Evaporator fan off maximum time
F4
30
Evaporator fan off time during
energy saving
F5
30
Evaporator fan on time during
energy saving
PAR.
DEF.
DIGITAL INPUTS
MIN. - MAX.
r1 to r2
MIN. - MAX.
-25°F/°C to 25°F/°C
-25°F/°C to 25°F/°C
0 = n/a
1 = NTC
0 = No
1 = Yes
0 = °C
1 = °F
0 = Disabled
1 = Evaporator probe (defrost
+ fan)
2 = Evaporator probe (fan)
3 = Condenser probe
0 = Cabinet temperature
1 = Setpoint
2 = Auxiliary temperature
0 s to 250 s : 10
MIN. - MAX.
1°F/°C to 15°F/°C
-99°F/°C to r2
r1 to 199°F/°C
0°F/°C to 99°F/°C
0 = Cooling
1 = Heating
0 = Asymmetric
1 = Symmetric
MIN. - MAX.
0 min to 240 min
0 min to 240 min
0 s to 240 s
0 min to 240 min
0 min to 240 min
0°F/°C to 199°F/°C
Differential = 4°F /2°C
0°F/°C to 199°F/°C
0 min to 15 min
MIN. - MAX.
0 h to 99 h
0 = only manual
If d8 = 3, maximum interval
0 = electric
1 = hot gas
2 = compressor stopped
-99°F/°C to 99°F/°C
0 min to 99 min
If P3 = 1, maximum duration
0 = No
1 = Yes
0 min to 99 min
0 = Cabinet temperature
1 = Display locked
2 = dEF label
0 min to 15 min
0 = Device on hours
1 = Compressor on hours
2 = Hours evaporator
temperature < d9
3 = Adaptive
-99°F/°C to 99°F/°C
0 = No
1 = Yes
0 min to 99 min
0 min to 999 min
If compressor on and
evaporator temperature < d22
0 = Only manual
0°F/°C to 40°F/°C
Optimal evaporation
temperature - d19
0 to 999 min
0 = Disabled
0°F/°C to 19°F/°C
Optimal evaporation
temperature + d22
MIN. - MAX.
0°F/°C to 99°F/°C
SP - A1
0 = Disabled
0°F/°C to 99°F/°C
SP + A4
0 = Disabled
0 min to 99 min x 10
0 min to 240 min
0 min to 240 min
0 min to 240 min
1°F/°C to 15°F/°C
MIN. - MAX.
0 = Off
1 = On
2 = On if compressor on
3 = Thermoregulated (with
F1)
4 = Thermoregulated (with
F1) if compressor on
-99°F/°C to 99°F/°C
Differential = 2°F /1°C
0 = Off
1 = On
2 = According to F0
0 min to 15 min
0 s to 240 s x 10
0 s to 240 s x 10
MIN. - MAX.

Advertisement

loading

Summary of Contents for Penn TC3B22

  • Page 1 Penn | TC3B22 | Installation Guide Rev. C | Part No. 24-7664-03566 | Page 1 of 2 | 19 January 2021 Basic Defrost Controller Installation Guide TC3B22 Basic controller for refrigerated cabinets, with energy-saving strategies FLASHING CONFIGURATION PARAMETERS Compressor on...
  • Page 2 Penn | TC3B22 | Installation Guide Rev. C | Part No. 24-7664-03566 | Page 2 of 2 | 19 January 2021 Door switch or multi-purpose input 0 = Disabled PRODUCT WARRANTY function 1 = Compressor + evaporator This product is covered by a limited warranty, details of which can be found at fan off, cabinet light on www.johnsoncontrols.com/buildingswarranty...