Alarms  
If the dehumidifier control system detects abnormal or unsafe for further operation situation, it issues Alarm 
(notification of such situation accompanied by respective component or entire dehumidifier stoppage and/or 
lockout) or Alert (notification of minor abnormal situation without any devices' stoppage or lockout). 
All alarms and alerts are recorded and can be viewed/cleared via the Touch Display OP:  
 Viewed: to facilitate troubleshooting and addressing abnormal situation 
 Cleared: to unlock stopped device or entire dehumidifier and allow for further operation 
The table F.1 below lists the basic alarms with their descriptions and recommended initial troubleshooting.  
Alarm 
No Air 
No air flow (air flow switch fault – if air flow 
switch is installed) 
Blower OL 
Main Blower overload/safety fault  
Fire 
Fire/smoke detector fault – if detector is installed 
externally and connected to control board 
Freeze 
Supply Air temperature is lower than Freezestat 
Setting (default: 45 F) 
Filter 
Alert, indicating that filter change timer has 
lapsed – if timer is activated 
VM 
Voltage Monitor fault – power supply (phasing, 
voltage etc.) is outside of pre‐set limits 
Compressor: 
Various compressor‐related alarms, relevant to: 
HP1‐(X)  
Compressor high/discharge pressure; 
LP1‐(X) 
Compressor low/suction pressure; 
SupHeat1 
Compressor superheat/suction temperature; 
DisTemp1 
Pool Water: 
Various compressor pool water heating‐related 
Water(X)1, 
alarms indicating inadequate (too low/too high) 
Wtr(X)1 
pool water flow and/or pool water temperature. 
HPRelief 
Alert, indicating that additional condensing 
capacity is engaged (pool water heat exchanger 
etc.) to prevent compressor high pressure from 
rising too high. 
 Note that proper and regular maintenance (example: keeping air filters and air‐side coils clean) should 
reduce the chances of abnormal operations, dehumidifier alarm‐related stoppages and downtime. 
 CAUTION!
 We recommend you have a qualified professional investigate and remedy all reoccurring 
alarm‐related stoppages and lock‐outs. Continuous dehumidifier restarting (clearing alarms) without addressing 
actual issues may result in equipment malfunction, premature wear, and failure. 
 
For more details regarding alarms and alerts, refer to the Alarms Description information (available via Help 
feature in Touch Display OP); contact factory if needed. 
 
 
F – Interface and Communication 
Table F.1. Most Common Alarms/Alerts 
Alarm Description 
 
2
F‐
 
 
Check 
Check main blower operation and air flow 
switch 
Check main blower operation and its LED 
light blinking pattern. 
Check external fire/smoke 
detector/system 
Check SA temperature readout, space 
heating system operation 
Clear the Filter alarm and cancel filter 
scheduler if not in use. 
Check Voltage Monitor info/status, 
incoming power (voltage) 
Check respective compressor‐related data 
(pressure and temperature readouts), 
refrigerant level in the receiver's sight 
glasses, cleanliness of air‐side coils and air 
filters. 
Unless the alarm occurred due to a known 
water flow interruption (backwash, etc.), 
check the pool water flow (pump, filters, 
valves) and pool water temperatures. 
No action required unless it's 
accompanied by other (compressor‐
related) alarm or faulty situation. 
 