Download Print this page
Schischek ExMax Series Installation Manual

Schischek ExMax Series Installation Manual

Hide thumbs Also See for ExMax Series:

Advertisement

Quick Links

ExMax
¼ turn actuators – size S
Electrical, explosion proof rotary actuators
3-pos. / 0...10 V DC / 4...20 mA control mode, with feedback, 24...240 V AC/DC, 95° angle of rotation
5/10 Nm, 15/30 Nm without and 5/10 Nm, 15 Nm with safety operation (spring return)
ATEX tested in acc. with directive 2014/ 34/ EU for zone 1, 2, 21, 22
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Torque
ExMax- 5.10 - Y
5 / 10 Nm
ExMax-15.30 - Y
15 / 30 Nm
ExMax- 5.10 - YF
5 / 10 Nm
ExMax-
15 - YF
15 Nm
ExMax- ... - CTS
Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
ExMax- ... - VAS
Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
Product views and applications
Safety damper
Ball valve
Description
The ExMax actuators are a revolution for safety, control and shut-off
dampers, VAV systems, ball valves, throttle valves and other motorized
applications for HVAC systems in chemical, pharmaceutical, industrial
and offshore/onshore plants, for use in Ex-areas zone 1, 2 (gas) and
zone 21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions,
only 3,5 kg weight, universal functions and technical data, an integrated
heater and an optional stainless steel housing guarantee safe operation
even under difficult environmental conditions. High quality brushless
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques as well as
spring return times, according to the actuator type, are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 V AC/ DC. Furthermore it is
possible to perform control signal inverting and compulsion control by
certain connections. The actuators are 100 % overload protected and
self locking.
...Max-...-YF actuators are equipped with spring return fail safe function.
Standard shaft connection is a double square direct coupling with
12 × 12 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
Supply
Motor running time
24...240 V AC/ DC
7,5 / 15 / 30 / 60 / 120 s/ 90°
24...240 V AC/ DC
7,5 / 15 / 30 / 60 / 120 s/ 90°
24...240 V AC/ DC
7,5 / 15 / 30 / 60 / 120 s/ 90°
24...240 V AC/ DC
7,5 / 15 / 30 / 60 / 120 s/ 90°
Throttle valve
Highlights
► For all type of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22
► Universal supply unit from 24...240 V AC/DC
►5 different motor running times 7,5 –15–30– 60 –120 s /90°, adjustable on site
► 2 different spring return running times ~ 3–10 s / 90°, selectable on site
► 3-pos. and 0...10 V DC, 4...20 mA control mode with or without spring return function
► Feedback signals 0...10 V DC and 4...20 mA
► Reverse function
► 5–10–15 –30 Nm actuators in the same housing size
► 100 % overload protected and self locking
► Compact design and small dimension (L × W × H = 210 × 95 × 80 mm)
► Direct coupling to the damper shaft with double square connection 12 × 12 mm
► 95° angle of rotation inclusive 5° pretension
► Robust aluminium housing (optional with seawater resistant coating) or in stainless steel
► IP66 protection
► Simple manual override included + preparation for comfortable manual override
► Gear made of stainless steel and sinter metal
► Weight only ~ 3,5 kg
► Integrated heater for ambient temperatures down to −40 °C
► Integrated safety temperature sensor
► Integrated equipment for manual adjustment (push button, lamp, switch)
► Preparation for adaptable and adjustable auxiliary switches type ...Switch
www.schischek.com
E X P L O S I O N P R O O F
Spring return Control mode
3-pos., 0...10 V DC, 4...20 mA
3-pos., 0...10 V DC, 4...20 mA
3 or 10 s/ 90°
3-pos., 0...10 V DC, 4...20 mA
3 or 10 s/ 90°
3-pos., 0...10 V DC, 4...20 mA
ExMax - ... - Y
ExMax - ... - YF
ExMax - ... - CTS
ExMax - ... - VAS
Subject to change!
Feedback
Wiring diagram
0...10 V DC, 4...20 mA SB 5.0 – 5.3
0...10 V DC, 4...20 mA SB 5.0 – 5.3
0...10 V DC, 4...20 mA SB 5.0 – 5.3
0...10 V DC, 4...20 mA SB 5.0 – 5.3
ExMax-S-Y_en
V01 – 16-Nov-2017
1 / 4

Advertisement

loading

Summary of Contents for Schischek ExMax Series

  • Page 1 ► Integrated equipment for manual adjustment (push button, lamp, switch) ► Preparation for adaptable and adjustable auxiliary switches type ...Switch ExMax-S-Y_en V01 – 16-Nov-2017 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 4...
  • Page 2 Cable glands nickel-plated № ТС RU С-DE.ГБ08.В.01510 Adaptions for dampers and valves on request ExMax-S-Y_en V01 – 16-Nov-2017 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 4...
  • Page 3 During commissioning apply a self adjustment drive. continue next page ExMax-S-Y_en V01 – 16-Nov-2017 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 4...
  • Page 4 Regard duty cycle at motor running times ! and failure indication Never use spring return actuators without external load. ExMax-S-Y_en V01 – 16-Nov-2017 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 4...

This manual is also suitable for:

Exmax 5.10 yExmax 15.30 yExmax 5.10 yfExmax 15 yfRedmax y seriesRedmax yf series ... Show all