Electrical Connection to 3152

Pressure Transmitter

Figure 2-7 – 356 wired to 3152
Terminal Block
1. Attach the designated wire to the positive terminal on the
3152 (see Figure 2-7).
2. Attach the designated wire to the negative terminal on the
3152 (see Figure 2-7).
3. If a ground wire (optional) is present, attach it to the ground
screw (see Figure 2-7).
4. Torque all screws (terminal and ground) to 7 in-lb (0.8 N-m).
NOTE
When installing onto 1150 Series pressure transmitters,
terminal and ground screws should be torqued to 5 in-lb
(0.6 N-m).
NOTE
When using the 356 Connector with devices other than
Rosemount transmitters, a fourth wire may be present. In
these cases, attach the wire and torque all screws in
accordance with the device product manual.