This section contains information that should be considered when
preparing to install the instrument side of the connector onto a
Rosemount 3152 Pressure Transmitter. Read this section carefully
before proceeding to installation procedure. Proper installation is
mandatory to assure qualification.
Always use plant-approved sealant when installing the 356
Connector onto the 3152 housing. During qualification, Loctite®
580™ (RNII part number 01153-0329-0001) was used.
Ensure the attached protective cover remains in place throughout
installation to provide protection from dust, moisture and other
foreign materials (see Figure 2-2). Once the instrument side is
connected to the field side of the connector, the cover may be
discarded.
Care must be taken to prevent the lead wires from becoming twisted
or cut during installation.