Xiria with Cable Test Facility – Operating instructions (EN)
This document is an addition to the general Xiria manual.
Refer to the manual for other operating instuctions.
With the Cable Test Facility (CTF) the primary cable can be tested up to 12kV without
opening the cable compartment door. This is done by replacing the integrated earth
connection with the test pins. Disconnecting the earthed connection and access to the test
connections with the test pins is only possible when the breaker is closed in earthed position
(Earthed cable position).
1) Switch the Xiria switchgear to Earthed cable position. See figure 1:
Figure 1: Earthed cable position
2) Open de CTF front cover plate by removing the padlock (if placed) and turn the front
knobs anti-clockwise. See figure 2:
Figure 2: Open de CTF front
Attention:
For safety reasons the CTF front cover plate is earthed with an earth wire. Do not
remove this wire.
3) Release the test connection openings by turning the interlock knob anti-clockwise in
vertical position and insert the test pin(s). See figure 3:
Figure 3: Turn the interlock and insert the test pin(s)
Document: 6095582 A
The test pins are now connected to a safe earthed contact
Attention:
Only the test pins supplied with the Xiria switchgear can be used. Do not use any
other test connection to perform
4) When the test pin is inserted, the integrated earth connection can be disconnected by
pulling the earth tube to the front. See figure 4:
Figure 4: Pull the earth tube to the front
5) The test voltage can now be applied to the cable via the test pin(s).
After finishing this test the earth tubes must be pushed back into the front for safely
earthing the test connections again.
6) To switch the Xiria switchgear back in Service position:
Push the earth tubes back into the front
Remove the test pin(s) from the test connection
Lock the access the the test connections openings by turning the interlock knob clockwise.
Put the CTF front plate in the upright closed position and lock it wht the front knobs and optionally
with the padlock.
7) Switch the Xiria switchgear in Service position. See figure 5:
Figure 5: Service position
www.eaton.eu/xiria
www.eaton.eu/xiria-e
Contact: xiria@eaton.com
Service Tel. +31 74 246 6888

Advertisement

loading
Need help?

Need help?

Do you have a question about the Xiria and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton Xiria

  • Page 1 With the Cable Test Facility (CTF) the primary cable can be tested up to 12kV without Only the test pins supplied with the Xiria switchgear can be used. Do not use any opening the cable compartment door. This is done by replacing the integrated earth other test connection to perform connection with the test pins.
  • Page 2 The Cable Test Facility (CTF) is earthed in Service position. Disconnecting the earthed connection of the CTF is not possible. The Xiria switchgear can be locked against opening with padlock S1. Earthed cable position: The CTF is safely earthed in Earthed cable position.