Mitsubishi Electric MELSEC iQ-R Series User Manual page 31

Analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■R60ADV8
*1
Shield
*1 For the wire, use the 2-core twisted cable.
*2 These values indicate the input resistance of the R60ADV8.
*3 Connect the AG terminal and the GND of the external device if there is a potential difference between them.
*4 Be sure to ground the shield wire of cables on each channel and the FG terminal.
■R60ADI8
*1
Shield
*1 For the wire, use the 2-core twisted cable.
*2 These values indicate the input resistance of the R60ADI8.
*3 Connect the AG terminal and the GND of the external device if there is a potential difference between them.
*4 Be sure to ground the shield wire of cables on each channel and the FG terminal.
Establish a connection of the FG terminal of the power supply module.
In the R60AD4 and R60ADV8, If the circuit is left open between terminals of unused channels, enabling A/D
conversion may generate an undefined digital value. To prevent this phenomenon, take any of the following
measures:
• Set the A/D conversion enable/disable setting in the unused channels to disable the A/D conversion. Note
that changing the A/D conversion enable/disable setting from A/D conversion enable to A/D conversion
disable causes a shorter sampling cycle.
• Short-circuit the input terminals (V+) and (V-) in the unused channels.
*2
V+
V-
AG
FG
*3
*4
*2
I+
250Ω
I-
AG
FG
*3
*4
500kΩ
500kΩ
500kΩ
500kΩ
6 WIRING
29
6.2 External Wiring
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r60ad4Melsec iq-r60adv8Melsec iq-r60adi8