Mitsubishi Electric MELSEC iQ-R Series User Manual page 30

Analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

External wiring examples
The following figures show the examples of external wiring.
■R60AD4
For voltage input
Signal source -10 to 10V
*5
For current input
Signal source 0 to 20mA
*5
*1 For the wire, use the 2-core twisted cable.
*2 These values indicate the input resistance of the R60AD4.
*3 For the current input, be sure to connect the terminals (V+) and (I+).
*4 Connect the AG terminal and the GND of the external device if there is a potential difference between them.
*5 Be sure to connect the shield wire of cables on each channel to the SLD terminal, and ground the FG terminal.
6 WIRING
28
6.2 External Wiring
*1
Shield
*3
*1
Shield
*5
*2
500k
V+
I+
V-/I-
500k
SLD
*2
500k
V+
I+
250
V-/I-
500k
SLD
AG
FG
*4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r60ad4Melsec iq-r60adv8Melsec iq-r60adi8

Table of Contents