Installation; Wiring; Permitted Sensors From Pilz - Pilz PDP20 F 4 mag Operating Manual

Table of Contents

Advertisement

PDP20 F 4 mag
Unit 2, O0/O1: Safety outputs of Unit 2
}
t
: Max. processing time for input when signal changes from "0" to "1"
}
1
t
: Typ. switch-on delay
}
2
t
: Max. processing time for semiconductor output when signal changes from "1" to "0"
}
3

Installation

The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail (35mm).
}
When installed vertically: Secure the unit by using a fixing element (e.g. retaining
}
bracket or end angle)
Push the device upwards or downwards before lifting it from the DIN rail.
}

Wiring

Please note:
Information given in the
}
Calculation of the max. cable length l
}
I
max
R
lmax
R
l
Use copper wiring with a temperature stability of 75 °C.
}
The power supply must comply with the regulations for extra low voltages with protect-
}
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.
1 wire may be connected per terminal. Use a terminal block if you need multiple con-
}
nections per terminal.
Ensure the wiring and EMC requirements of IEC 60204-1 are met.
}

Permitted sensors from Pilz

PSENmag:
}
PSENhinge
}
PSENrope
}
Operating Manual PDP20 F 4 mag
24737-EN-03
"Technical details [
R
lmax
=
R
/ km
l
= max. overall cable resistance (see
 / km = cable resistance/km
PSEN 1.1p-10, PSEN 1.1p-20
PSEN ma1.3-20 M12, PSEN ma1.3a-20, PSEN ma1.3b-20, PSEN ma1.3b-23,
PSEN ma1.3n-20, PSEN ma1.3p-20
PSEN ma1.4-51 M12, PSEN ma1.4a-50, PSEN ma1.4a-51, PSEN ma1.4n-50,
PSEN ma1.4n-51, PSEN ma1.4p-50, PSEN ma1.4p-51
PSEN hs1.1p
PSEN hs1.2p
PSEN rs1.0
PSEN rs2.0
13]" must be followed.
in the input circuit:
max
Technical details [
13])
9

Hide quick links:

Advertisement

Table of Contents
loading