bUILt-IN GaS LINE LoCatIoNS
Note: Leave an access in the "island" structure for gas supply and regulator service
that is not inside the grill structure. Note: Area should be kept clear of sharp, jagged, or
extremely abrasive surfaces to avoid possible damage to gas supply lines. Exercise
caution when pulling gas lines through built-in structure.
1
3
2
built-iN Gas liNe locatioNs
S-460™
4
3
4
1
(120.65 mm)
6
1
4
2
(158.8 mm)
2
1
3
2
(63.5 mm)
a
b
c
table
maximum Capacity of metallic pipe in Cubic feet of Gas per Hour for Gas pressures of 2 psi or Less and
6.2(a)
Nominal
actual
Iron pipe
Id:
Size
(Inches)
10
(Inches)
1/2
.622
131
3/4
.824
273
1
1.049
514
1 1/4
1.380
1,060
1 1/2
1.610
1,580
2
2.067
3,050
2 1/2
2.469
4,860
3
3.068
8,580
4
4.026
17,500
© 2009 National Fire Protection Association, Inc. and International Approval Services - U.S., Inc. All Rights Reserved.
www.weber.com
®
a
1
2
c
3
b
S-660™
toLEraNCES
4
+
(3.8mm)
3
1
4
8
(120.65 mm)
-
(3.8mm)
1
8
6
+
(3.8mm)
1
1
4
8
(158.8 mm)
-
(3.8mm)
1
8
2
+
(3.8mm)
1
1
2
8
(63.5 mm)
-
(3.8mm)
1
8
Plan View Left
Side View
Gas Inlet
a pressure drop of 0.3 Inch water Column. (based on a 0.60 Specific Gravity Gas)
20
30
40
90
72
62
188
151
129
353
284
243
726
583
499
1,090
873
747
2,090
1,680
1,440
3,340
2,680
2,290
5,900
4,740
4,050
12,000
9,660
8,270
Gas suPPlY
tYpICaL NatUraL GaS SUppLY INStaLLatIoN
We recommend that this installation be done by a LICENSED professional.
GENEraL SpECIfICatIoNS for pIpING
Note - Contact your local municipality for building codes regulating outdoor gas grill
installations. In absence of Local Codes, you must conform to the latest edition of
National Fuel Gas Code ANSI Z223.1/NFPA54.
This grill is designed to operate at 4.5 inches of water column pressure.
A manual shut-off valve must be installed outdoors, and be accessible, not in the
"built-in" structure. An additional manual shut-off valve indoors should be installed
in the branch fuel line in an accessible location near the supply line.
m
CaUtIoN: If young children are in the area, a locking valve should
be considered.
Pipe compound should be used which is resistant to the action of liquid propane
gas when gas connections are made.
The gas connections must be firmly attached to a rigid, permanent construction.
Note: The information provided in this manual is general for typical installations. We
cannot cover all possible installation ideas. We recommend, prior to installation, that you
contact your municipality for local building codes and your local fire department for
installation verification.
If you have any questions, contact Customer Service at 1-800-446-1071.
GaS LINE pIpING
Refer to piping chart.
The corrugated gas line from the manifold is 58 inches (1,473.2 mm) long. Do not
extend the gas line.
We have provided the means to make an SAE 45° flare connection. Do not use
pipe sealant on this connection.
If the length of line required does not exceed 50 feet, use a 5/8" O.D. tube. One
size larger should be used for lengths greater than 50 feet. Refer to piping chart.
Gas piping may be copper tubing, type K or L; polyethylene plastic tube, with a
minimum wall thickness of .062 inch (1.57 mm); or standard weight (schedule 40)
steel or wrought iron pipe.
Copper tubing must be tin-lined if the gas contains more than 0.3 grams of
hydrogen sulfide per 100 cubic feet of gas.
Plastic tubing is suitable only for outdoor, underground use.
Gas piping in contact with earth, or any other material which may corrode the
piping, must be protected against corrosion in an approved manner.
Underground piping must have a minimum of 18" cover.
Length of pipe (feet)
50
60
70
80
55
50
46
42
114
104
95
89
215
195
179
167
442
400
368
343
662
600
552
514
1,280
1,160
1,060
989
2,030
1,840
1,690
1,580
3,590
3,260
3,000
2,790
7,330
6,640
6,110
5,680
90
100
125
150
40
38
33
30
83
79
70
63
157
148
131
119
322
304
269
244
482
455
403
366
928
877
777
704
1,480
1,400
1,240
1,120
2,610
2,470
2,190
1,980
5,330
5,040
4,460
4,050
23
23
175
200
28
26
58
54
109
102
224
209
336
313
648
602
1,030
960
1,820
1,700
3,720
3,460