Danfoss VLT Design Manual page 16

Refrigeration drive
Hide thumbs Also See for VLT:
Table of Contents

Advertisement

Introduction
2.6.2 Safe Stop Installation
To carry out an installation of a Category 0 Stop
(EN60204) in conformity with Safety Category 3 (EN954-1),
follow these instructions:
1.
The bridge (jumper) between Terminal 37 and 24
V DC must be removed. Cutting or breaking the
jumper is not sufficient. Remove it entirely to
avoid short-circuiting. See jumper in
Illustration 2.2.
2.
Connect terminal 37 to 24 V DC by a short-circuit
protected cable. The 24 V DC voltage supply
must be interruptible by an EN954-1 Category 3
circuit interrupt device. If the interrupt device and
the frequency converter are placed in the same
installation panel, use an unscreened cable
instead of a screened one.
Illustration 2.2 Bridge Jumper between Terminal 37 and 24 V DC
®
VLT
Refrigeration Drive Design Guide
Illustration 2.3 shows a Stopping Category 0 (EN 60204-1)
with safety Category 3 (EN 954-1). The circuit interrupt is
caused by an opening door contact. The illustration also
shows how to connect a non-safety related hardware
coast.
®