General Specifications and ...
Frequency converter, P4K0, T4
Cable
length [m]
5
50
150
Table 8.19
Frequency converter, P7K5, T4
Cable
length [m]
5
50
150
Table 8.20
Frequency converter, P11K, T4
Cable
length [m]
8
8
15
100
150
Table 8.21
Frequency converter, P15K, T4
Cable
length [m]
36
100
150
Table 8.22
Frequency converter, P18K, T4
Cable
length [m]
36
100
150
Table 8.23
Frequency converter, P22K, T4
Cable
length [m]
36
100
150
Table 8.24
120
®
VLT
Refrigeration Drive Design Guide
Mains
Rise time
voltage [V]
[μsec]
400
0.172
400
0.310
400
0.370
Mains
Rise time
voltage [V]
[μsec]
400
0.04755
400
0.207
400
0.6742
Rise time
Mains
voltage [V]
[μsec]
400
0.408
400
0.364
400
0.400
Rise time
Mains
voltage [V]
[μsec]
400
0.422
400
0.464
400
0.896
Mains
Rise time
voltage [V]
[μsec]
400
0.344
400
1.000
400
1.400
Rise time
Mains
voltage [V]
[μsec]
400
0.232
400
0.410
400
0.430
®
MG16G102 - VLT
Vpeak
[kV]
0.890
1.190
Vpeak
[kV]
0.739
1.040
1.030
Vpeak
[kV]
0.718
1.050
0.980
Vpeak
[kV]
1.060
0.900
1.000
Vpeak
[kV]
1.040
1.190
1.040
Vpeak
[kV]
0.950
0.980
0.970
is a registered Danfoss trademark
dU/dt
[kV/μsec]
4.156
2.564
1.770
dU/dt
[kV/μsec]
8.035
4.548
2.828
dU/dt
[kV/μsec]
1.402
2.376
2.000
dU/dt
[kV/μsec]
2.014
1.616
0.915
dU/dt
[kV/μsec]
2.442
0.950
0.596
dU/dt
[kV/μsec]
3.534
1.927
1.860